Prior to installation, HVI
Â
mage or any other defect is found, HVI
of HVI
power Conductors must not be damaged by compressive deformation or cuts.
®
When using HVI
®
Â
tection measures must be taken.
If HVI
power Conductors are installed on thatched roofs (e.g. reed, straw), special installation
®
Â
conditions have to be observed for these flammable locations. In our Lightning Protection / Earthing
main catalogue (HVI Lightning Protection for Thatched Roofs), the special installation conditions for
HVI Conductors are described. These conditions also apply to HVI
If the supporting tube is led through a roof, the roof must be properly sealed. Warm roofs must be
Â
properly sealed and insulated.
HVI
power Conductors are suitable for outdoor use and can be installed downstream of the
®
Â
sealing end e.g. on roofs, in walls, in concrete (mechanically protected, if required) or on facades /
facade constructions. However, the conductors are not suitable for permanent exposure to moisture.
HVI
power Conductors must not be installed in the soil.
®
Soiled HVI
power Conductors can be cleaned with a cloth soaked with a special cleaning agent
®
Â
(Part No. 297 199). To be able to comply with dangerous goods regulations, this product is only
transported within Germany and Austria. ISOPROPYL ALCOHOL (99.1 to 99.9 %) (CSA No. 67-63.0)
can be used as an alternative!
HVI
power Conductors must not be painted due to the special design of the outer sheath.
®
Â
The function of HVI
Â
they do not have a magnetic shielding effect. Induction effects in secondary conductors / loops must
be observed. If required, surge protection measures must be taken.
For application-specific questions, please contact the relevant sales team or the DEHN representati-
Â
ve in your country.
It has not yet been checked whether HVI
Â
areas. Therefore, it is not allowed to use HVI
power Conductors must be examined for good order and condition. If da-
®
power Conductors in potentially explosive atmospheres, fire and explosion pro-
power Conductors is to maintain the separation distance. Due to their design,
®
power Conductors must not be installed. The black sheath
®
power Conductors are suitable for use in hazardous
®
power Conductors in these areas.
®
power Conductors.
®