Herunterladen Diese Seite drucken

Johnson Controls VG8000N Anleitung Seite 39

Vorschau ausblenden Andere Handbücher für VG8000N:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

121 4349 050 E
Danger analysis in accordance with the pressure equipment and machine directive
Danger
Description of parts:
Function:
Fault diagnosis
Cracks,
Holes,
Leakage, flying shrapnel,
Damage,
danger of poisoning,
Leakage
burns danger, corrosive
fluids danger,
Environmental pollution
Broken flanges
Description of parts:
Function:
Flange fittings
leakage danger of
not tight,
poisoning, burns danger,
leakage
corrosive fluids danger,
Environmental pollution
Hot surface
Burns danger
The TRB 700 and general safety regulations must be observed unconditionally
during repair.
Qualified personnel must always be present when repair and maintenance are
carried out (see paragraph "Qualified Personnel").
Valve housing, bonnet, pipe piece
Pressurised parts
Effects
Piping stressed beyond permitted
limits, recoil forces, pressure
surges, valve used as fixed point,
permitted pressure and
temperature limits not observed
Improper transport, bending
stresses too great, thermal stress
Valve without actuator
Flow control
Flange fittings loosen under
pressure, bolts not tightened
diagonally
Valve without insulation, carrying
hot fluid, too easily reached
Cause
Reduce pressure and
stress, change piping
position, install
compensators, select other
materials, replace valve
replace valve, ensure that
piping is laid free of stress
or tension
Proper installation in
accordance with these
operating instructions
Insulate valve or install
protective device
17 E
Remedial action/
Minimising risk

Werbung