2 E
Technical data
Nominal pressure rating:
Fluid temperature range:
Face to face dimensions:
Flange dimensions:
(Recommended) Pre-welded flange:
Body material:
Stem, plug, and seat edge:
Welded seat edge:
Flow characteristics:
Leakage rate:
Packing (silicon free):
Valve sizes to k
vs
Stroke
DN
0.1* 0.16* 0.25*
k
-Value
0.4 0.63 1.0
vs
1.6 2.5 4.0
* 0.1 to 0.25 k
- coefficient only available with two-way valve (PDTC) = Needle plug
vs
** PDTO. Valves available only with DN15, DN25 and DN40. DN15 first available at 0.63 k
( ) Reduced k
coefficient
vs
Operation:
PDTC
Bild_021b
Mixing
Bild_021d
Caution: Pressure test of the heating installation may only be performed with opened valves.
Valve size:
DN 15...150
PN16
-10°C to 180°C
DN125 and 150 Limitations as per DIN 4747 & DIN 4752
In accordance with EN558-1 Table 1column 1
In accordance with DIN 1092-2, B Form seal strip
In accordance with DIN 1092-2
Nodular cast iron: DIN EN 1563: abbr. code: EN-GJS-400-15
Spec. No.: EN-JS1030, zinc plated
Stainless steel spec. -No.: 1.4305
Stainless steel spec. -No.: 1.4305, Patented by Johnson Controls
Two-way valve:
Mixing valve:
Diverting valve:
Choice of any plug arrangement (special model)
Plug:
Stainless steel hollow cylinder Spec. -No.: 1.4305
Rangeability:
100:1, 25:1 at 0.63 k
Max. 0.05% of k
Max. ∆p
DN 65: 500 kPa, DN 80: 400 kPa, DN 100: 300 kPa, DN 125: 200 kPa,
:
v100
DN 150: 100 kPa, with super heated steam 800 kPa (valve fully open)
Spring loaded Teflon/Viton/Teflon
Spring loaded Aramid fibre/Viton/ Aramid fibre (Teflon free model)
coefficients:
13mm
15**
20
25**
6,3
10
(4,0)
(6,3)
Two-way valve
PDTO
E
Bild_021c
Diverting
E
L
Bild_021e
Equal percent
Equal percent / linear
linear / Equal percent
0.4 k
vs,
vs
; test process with water as per DIN EN1349
vs
32
40**
50
16
25
40
(10)
(16)
(25)
The following is valid for the flow direction:
Valve plug close-off movement must always be
directed against the flow. This requirement is
fulfilled if the valve is installed as directed by the
arrow on the valve body.
E
Note:
L
With mixing valves, the through flow should be
used for regulating and with diverting valves, the
bypass flow should be used (equal percent).
E
E = Equal percent
L = Linear
, 0.25 k
, 0.16 k
& 0.1 k
vs
vs
25mm
42mm
65
80
100
63
100
160
(40)
(63)
(100)
121 4349 050 E
coefficient
vs
125
150
250
350
(160)
(250)
-coefficient
vs