Actuator mounting and removal information:
The control valve is normally supplied complete with actuator. It is not permitted to remove or replace an
actuator on systems in operation, under operating temperature and pressure. Service or modification should
be carried out in accordance with the actuator SDI. During mounting procedure the plug should NOT be
rotated with downward pressure. Ensure adherence to max. valve operating forces when replacing actuator.
These are:
Commissioning:
Prior to commissioning check information on material, pressure, temperature and flow direction in
conjunction with the installation piping system plan.
Follow TRB 700.
Impurities in the piping system and valves, such as dirt, welding beads etc. will cause the system to leak.
Prior to commissioning a new installation or re-commissioning after repairs or service, ensure that:
Correct installation- and assembly work has been completed.
Only qualified personnel carry out commissioning.
Correct functional position of the valve is ascertained.
Maintenance of existing protective facilities is carried out.
Maintenance, service and conversion:
Repair parts:
Standard – Packing:
Valve size DN 15 - 40
Valve size DN 50 - 80
Valve size DN 100 - 150
Packing for Teflon free valves:
Valve size DN 15 - 40
Valve size DN 50 - 80
Valve size DN 100 - 150
*Glycerine-Packing for:
Valve size DN 15 - 40
Valve size DN 50 - 80
Valve size DN 100 - 150
*Installation kit necessary!
Glycerine: available at any chemist
Trouble-free fitting without damaging the packing parts can only be
achieved with the relevant montage kit
For more spare parts see VG8000N parts list
Valve removal:
In addition to generally valid installation directives and the TRB 700, the following points
should be observed:
Pressure free piping system
Cooled fluid
Drained piping system
Danger
With corrosive or otherwise aggressive fluids the pipe system should be ventilated.
Work to be performed by qualified personnel only.
2000N for valve sizes DN 15 - 40
6000N for valve sizes DN 50 - 80
8600N for valve sizes DN 100 - 150
Order No. 121 4393 011
Order No. 121 4409 011
Order No. 121 4433 011
Order No. 121 4493 021
Order No. 121 4409 021
Order No. 121 4433 021
Order No. 121 4434 011
Order No. 121 4435 011
Order No. 121 4436 011
Order No. for installation kit
121 4434 111
121 4435 111
121 4436 111