6.5 Venting the safety storage cabinet
6.5.1 Connection to an exhaust air system
WARNING!
Insufficient air circulation in the safety storage cabinet
A lack of or insufficient air exchange can lead to formation of an explosive
atmosphere in the safety storage cabinet.
This can lead to death or serious injury.
–
In a safety storage cabinet with industrial ventilation, the minimum hourly air
exchange must be at least 30 m³/h when the doors are closed.
Installation of industrial ventilation and connection to an existing exhaust air
i
system must be carried out by a qualified company and is not a service provided
by DÜPERTHAL.
Connection to the exhaust air system:
Personnel:
▪
Technically qualified personnel
➔
Connect the exhaust air line to the exhaust air connection socket and secure with a
collar.
➔
After installing the safety storage cabinet, check the connection to the exhaust air system
with smoke tubes.
The power of the exhaust air system can be determined using the technical
i
specifications,
68
DISPOSAL UTS ergo, DISPOSAL BENCH
Chapter 3.3 "Druckabfall bei Entlüftung" on page 55.
Operating instructions