Operation

Operating the product is limited to its regular monitoring:
The green LED is on
The red LED is off
7.1
Alarm
If the probe detects liquid, the electrical output signal of the probe changes
and the control unit triggers an alarm.
The red LED lights.
The audible alarm sounds.
The alarm signal is transmitted to additional equipment via the relay output.
In the case of products with an EnOcean® wireless module, the control unit
sends a message to the AFRISOhome gateway. The user receives a mes-
sage from the AFRISO app that liquid has been detected.
7.1.1
Acknowledging an alarm
1. Press the acknowledge key at the control unit.
1. The audible alarm is switched off.
- The red LED remains lit.
Power outage
No alarm is triggered in case of a power outage. When mains voltage is
restored, the product immediately resumes operation. If, during the power
outage, leakage has occurred, the product triggers an alarm once power
is available again.
7.1.2
After an alarm
After an alarm, the probe must be checked for pollution.
Verify that there are no remainders of the liquid or deposits on the
probe.
1. Remove remainders of liquid.
2. Carefully clean the probe with a dry, lint-free cloth.
3. Perform a function test.
Operation