6
Commissioning
6.1
Connecting the product to an AFRISOhome gateway (optional)
See the operating instructions of the AFRISOhome gateway or the app for
detailed information on establishing a wireless connection.
 Verify correct electrical connection of the control unit (see chapter "Elec-
trical connection").
 Verify that AFRISOhome gateway is in the vicinity of the product.
 Verify that the AFRISOhome gateway is in "Learn" mode.
1. Apply mains voltage.
- The green LED is on.
2. Briefly press the lower key once.
- The product sends a Learn telegram (LRNTEL).
- The product is now connected to the AFRISOhome gateway.
3. Note the instructions/information in the app.
6.2
Function test
6.2.1
At the probe
Verify that the liquid to be detected is detected at all temperatures that
may be present at the installation site.
1. Submerge the probe into the liquid to be detected.
- The red LED lights up and the audible alarm sounds.
2. Press the acknowledge key at the control unit.
- The audible alarm is switched off.
- The red LED lights.
3. Remove the probe from the liquid.
- The red LED goes off.
6.2.2
At the control unit
1. Press the Test key
- The red LED lights up and the audible alarm sounds.
2. Release the Test key to terminate the function test at the control unit.