Alarms and faults

16
PROBLEM
ALARM SIGNAL
POWER LED off
POWER LED off
The barrier does
not open or close.
POSSIBLE CAUSE
This message is not visible if
mode.
fault.
Controller initialisation failed.
Overcurrent detected in in-
verter.
SEC1 and SEC2 of the trans-
former.
Travel data acquisition error.
Calibration procedure failed
(
).
Automation system position
.
error.
CORRECTIVE ACTION
Replace fuse.
Replace fuse.
We recommend replacing the control unit if the
problem persists.
Press the TEST
mand requests in succession.
the barrier unlocked.
Press TEST and check if any safety devices are
in alarm state.
Repeat acquisition procedure.
during self-acquisition.
sition procedure.
SX
-
right hand opening barriers
barrier relative to passage seen from inspection
hatch side). If the position is changed and mes-
sage
• Adjust the spring position correctly for the re-
quired opening direction.
• Press and hold PROG until
and
appears on the display.
Repeat acquisition procedure.
Check the motor cable.
• Check the setting of par.
• Check the correct ACS/BA/60 system connec-
tion to the control unit.
• Re-engage the boom.
• Consider replacing the boom if it is damaged.
-
-
-
. Repeat acqui-
DX
(position of
disappears
.
...Continued