Connection Notes

Switching Logic (switch-selectable voltage)
Switching Logic (non-switch selectable)
Alarm output - Fail-safe option
Page EN-12
Downloaded from
www.Manualslib.com
Before opening the lid, ensure there are no dust deposits around the SITRANS LPS200.
Ensure that the atmosphere around SITRANS LPS200 is settled.
Use a fuse for the signal output (max. 6 A).
Make sure the main voltage does not exceed the maximum voltage listed on the
product label and the setting of the voltage selector.
In case of inexpert handling or handling malpractice, the electric safety of the
device cannot be guaranteed.
Provide protection for relay contacts to protect the device against spikes if inductive
loads are connected.
LED
red
No
Fault
Fault
LED 2
LED 2
off
red
SITRANS LPS200 – OPERATING INSTRUCTIONS
manuals search engine
LED
green
Connection example
Full detector with fail-safe option.
Output signal signals a fault if level reaches
high level switching point, the main voltage
fails, there is a faulty connection, or if the
unit is faulty.
signal
output
7ML19985FS62