Assembly, Installation and operation
4
Assembly
EN
4.1
Assembly instructions
The leak sensor is assembled as shown in fig. 2, fig. 3, fig. 4 or fig. 5.
Note:
Mounting bracket PS 4597.000 in conjunction with the cable ties supplied loose may be
used to attach the sensor probe close to the floor (see fig. 2, item 4).
5
Installation and operation
5.1

Operating and display elements

The operating and display elements are shown in fig. 6.
Key to fig. 6
1
Multi-LED for status display
2
CAN bus connection, 24 V
3
CAN bus connection, 24 V
4
Universal interface
5
Sensor probe with cables
5.2
Installation
Connect the sensor probe connector to the universal interface (fig. 6, item 4).
Lay the sensor to the measuring point.
Fit the sensor probe so that the contacts are pointing vertically downwards towards the floor.
Note:
In order to be able to detect leaks rapidly, the contacts of the sensor probe should be
fitted as close as possible to the floor, approximately 1 to 2 mm above it.
Connect the leak sensor to the CMC III PU or to the neighbouring elements in the CAN bus using a
CAN bus connection cable (fig. 6, items 2, 3).
Status change display:
– The two green and the two red CAN bus LEDs on the CAN bus connection of the leak sensor will
start to flash.
– The multi-LED of the processing unit flashes continually in the sequence green – orange – red.
– The multi-LED of the leak sensor flashes blue continuously.
Press the "C" key on the CMC III PU (an initial audio signal will sound) and keep it pressed for approx.
3 seconds until a second audio signal is heard.
Status change display on the CAN bus LEDs:
– Continuous green LEDs: CAN bus status "OK".
– Continuous red LEDs: CAN bus status "faulty".
Status change display on the multi-LED of the processing unit:
– Continuous green light: All devices connected to the CAN bus have the status "OK".
– Continuous orange light: At least one device connected to the CAN bus has the status "Warning".
– Continuous red light: At least one device connected to the CAN bus has the status "Alarm".
8
Rittal CMC III leak sensor