Herunterladen Inhalt Inhalt Diese Seite drucken

Output Signals; Switching Outputs; 1Twopoint Mode - Switch Point Setting (Sp) - HYDAC EDS 3000 Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für EDS 3000:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

EDS 3000 IO-Link
9

Output Signals

9.1

SWITCHING OUTPUTS

The EDS 3000 IO-Link has 2 switch outputs whose switching behaviour (window mode or
twopoint mode) is parameterisable.
In addition to the IO-Link Smart Sensor Profile Specification, a switch and switch-back
delay can be set in HYDAC IO-Link sensors.
CAUTION
Exceeding or falling below the measuring range leads to a limitation to the
corresponding upper or lower limit of the measuring range.
9.1.1
Twopoint mode - Switch point setting (SP)
One switch point and one switch-back point can be set for each switching output. The
particular output will switch when the pre-set switch point is reached and then switch back
when the level drops below the switch-back point.
Example for switch point 1 (N/C and N/O function):
Normally open function
Normally closed function
Abbreviations:
"SP1", "SP2"
"RP1", "RP2"
"HNO",
"HNC"
NOTICE:
• It is only possible to set the switch point (SP) if it is higher than the respective
switch-back point (RP).
Edition: 2014-11-06
On
Off
On
Off
= switch point 1 / switch point 2
= switch-back point 1 / switch-back point 2
= N/O when hysteresis function is active
= N/C when hysteresis function is active
HYDAC ELECTRONIC GMBH
9
Part No.: 669897 E

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis