6. Electrical work
TEMP.
MENU
BACK
MONITOR/SET
PAR-21MAA
CHECK
ON/OFF
TEMP
FAN
AUTO STOP
MODE
VANE
AUTO START
CHECK
LOUVER
h
TEST RUN
min
SET
RESET
CLOCK
Function table
Select unit number 00
Mode
Power failure automatic recovery
Indoor temperature detecting
LOSSNAY connectivity
Power voltage
10
Downloaded from
www.Manualslib.com
ON/OFF
ON/OFF
FILTER
DAY
CHECK
TEST
CLOCK
OPERATION
CLEAR
Fig. 6-8
CHECK
CHECK
Fig. 6-9
Settings
Not available
Available
Indoor unit operating average
Set by indoor unit's remote controller
Remote controller's internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
240 V
220 V, 230 V
manuals search engine

6.3. Function settings

6.3.1. Function setting on the unit (Selecting the unit functions)
Mode number
1) For wired remote controller (Fig. 6-8)
Setting number
Changing the power voltage setting
Refrigerant address
• Be sure to change the power voltage setting depending on the voltage used.
Unit number
1 Go to the function setting mode.
Switch OFF the remote controller.
Press the FILTER A and TEST RUN B buttons simultaneously and hold
them for at least 2 seconds. FUNCTION will start to blink.
2 Use the C buttons to set the refrigerant address (3) to 00.
3 Press D button and [--] will start to blink in the unit number (4) display.
4 Use the C buttons to set the unit number (4) to 00.
5 Press the MODE button E to designate the refrigerant address/unit number. [--]
will blink in the mode number (1) display momentarily.
6 Press the F buttons to set the mode number (1) to 04.
7 Press the G button and the current set setting number (2) will blink.
Use the F button to switch the setting number in response to the power supply
voltage to be used.
Power supply voltage
8 Press the MODE button E and mode and the setting number (1) and (2) will
change to being on constantly and the contents of the setting can be confi rmed.
9 Press the FILTER A and TEST RUN B buttons simultaneously for at least 2
seconds. The function selection screen will disappear momentarily and the air
conditioner OFF display will appear.
2) For wireless remote controller (Fig. 6-9)
Changing the power voltage setting
CHECK
• Be sure to change the power voltage setting depending on the voltage used.
1 Going to the function select mode
CHECK
Press the
(Start this operation from the status of remote controller display turned off.)
CHECK
is lighted and "00" blinks.
Press the
ler toward the receiver of the indoor unit and press the
2 Setting the unit number
CHECK
Press the
wireless remote controller toward the receiver of the indoor unit and press the
min
button B.
3 Selecting a mode
Enter 04 to change the power voltage setting using the
and D. Direct the wireless remote controller toward the receiver of the indoor
unit and press the
Current setting number:
4 Selecting the setting number
Use the
01 (240 V). Direct the wireless remote controller toward the sensor of the indoor
unit and press the
5 To select multiple functions continuously
Repeat steps 3 and 4 to change multiple function settings continuously.
6 Complete function selection
Direct the wireless remote controller toward the sensor of the indoor unit and
press the
Note: Whenever changes are made to the function settings after installation
or maintenance, be sure to record the changes with a mark in the "Setting"
column of the Function table.
6.3.2. Function setting on the remote controller
Refer to the indoor unit operation manual.
240 V
: setting number = 1
220 V, 230 V : setting number = 2
button F twice continuously.
temp button C once to set "50". Direct the wireless remote control-
temp buttons C and D to set the unit number "00". Direct the
h
button A.
1 = 1 beep (1 second)
2 = 2 beeps (1 second each)
3 = 3 beeps (1 second each)
temp buttons C and D to change the power voltage setting to
h
button A.
button E.
Mode no.
Setting no. Initial setting
1
01
w
2
1
02
2
3
1
03
2
3
1
04
2
h
button A.
temp buttons C
setting
Ο
Ο
Ο
Ο