WARNINGS
!
When electrical devices are being operated, certain parts of these devices are live and can therefore constitute a hazard. Incorrect
handling of these devices can therefore lead to death or serious injury as well as to considerable damage to property. Only
suitably qualified specialist personnel are permitted to work on or near this device. Fault-free and safe operation of this device
presupposes correct transportation, storage, installation and assembly.
CAUTION
Electrostatic sensitive devices (ESD). Only trained personnel are permitted to open the device.
Description and design
The SITOP power flexi is a build-in device. When the device is being installed, the relevant DIN/VDE stipulations or the country-specific
regulations are to be complied with.
Primarily pulsed power supply units for mounting on standard mounting rails to DIN EN 50022-35x15/7,5.
For connection to single-phase AC power supply system, 120 or 230V, 50/60Hz.
The output is idling-proof, short-circuit proof, floating and adjustable.
Technical method of operation
The output voltage of the device can be set to between 3 V
front (see Page 2 for position) or externally by means of terminals X2-2 (see Page 4).
The device works in the output voltage range from 3 to 12 V
In the output voltage range 12 to 52 V
The current can be limited to between 2 A and 10 A. Current limitation is set by means of a potentiometer I
externally by means of terminals X2-12 (see Page 4).
Technical data
Input variables
Rated input voltage:
120/230V, 50/60Hz
Working-voltage range:
85-132V
170-264V
Overvoltage resistant to EN 61000-4-1 A.2
Efficiency under full load and at 230 V:
> 75%
Making-current limitation (25°C) as standard
at 230 V AC:
2
< 32A, 0.8A
s
Recommended circuit-breaker on supply side
6A Charact. C.
Input current at 120/230 V:
2.2/0.9A
Power input:
138 W
Weight
0.9kg
Installation notes
The device is to be mounted vertically for correct cooling so that the input terminals and the output terminals are at the bottom. A space of at least
50 mm is to be kept free above and beneath the device.
The supply voltage (120/230 V AC) and the necessary jumper for the 120 V range must be connected in accordance with VDE 0100 and VDE
0160. A protective device (fuse) and a disconnecting device for isolating the unit from the power supply must be provided.
Before installation or maintenance work, the main switch on the unit is to be switched off and secured against accidental switch-on. If the
event of non-compliance with this condition, touching of live parts can lead to death or serious injury.
When the device is operated in the 120 V range, a jumper must be wired between the two "AC120V-JUMPER" terminals. This must have the
same cross-section and insulation as the power supply leads. Its length must not exceed 100 mm.
Caution: The jumper which is needed is also live and therefore hazardous.
Siemens AG Österreich
Printed in Austria
and 52 V
DC
with a max. output current of 10 A.
DC
, the power output is limited to a maximum of 120 W (see characteritic curve, Page 7).
DC
Output variables
Output DC voltage:
Status as delivered: 24 V ±1% (rated voltage),
adjustable by means of screwdriver at
U
potentiometer
(front of device. For position, see
A
Page2) in the range 3 to 52 V
Ripple of the output voltage:
< 50 mV
residual ripple
ss
< 100 V
switching peaks
ss
Output DC current:
max. 10 A (in the range 3 to 12 V)
Output power:
max. 120 W (in the range 12 to 52 V)
Output-current limitation:
Status as delivered:10 A ±10%,
adjustable by means of screwdriver at
I
potentiometer
Amax
see Page 2) in the range 2 to 10 A.
Environment
Temperature
For storage and transport: -25 to +85 °C
For operation from 97 to 132 V and 195 to 264 V; 0
Up to +60°C , from 170 to 180 V derating t
+1K/V∼ and for operation from 85 to 90 V derating
t
+2K/V∼
amb
Humidity class :
Corresponding climatic category 3K3 to EN 60721
Self-cooling, air
. The output voltage is adjusted by means of a potentiometer U
DC
(front of device. For position,
amb
(see Page 2 for position) or
Amax
Protection and monitoring function
Static power limitation: type. 1.1 x P
Behaviour in the event of a short-circuit (output):
automatic re-start
Mains buffering at an input voltage of 93/187 V and
output power of 120 W:
>10 ms
Built-in fuse:
T 3,15A/250V
Regulations
Degree of protection: IP20 to IEC 529
Class of protection: 1 to IEC 536
Safety to VDE 0160 and VDE 0805 (EN60950):
SELV
Emitted interference: to EN 50081-1, radio
interference suppression to EN 55022, limit-value
curve B
Immunity to inteference: to EN 50082-2 incl. Table
A4
Limitation of input-current harmonics to EN 61000-
3-2
UL acceptance inspection in preparation
Bestell-Nr.:C98130-A7518-A1-02-19