CONFIGURING THE ENERGYMIZOR 2 (MODULATE TYPE)
PROG / CODE ENG / 4) SET UP / 1) CONFIG / MODULATION <2>
In modulation mode, you can set the temperature band where the control will modulate the from 10v to 0v.
The heat output remains active.
You are now prompted to enter the differential setting
With a differential of 02, the Energymizor will start to modulate
2°C degrees below the set temperature.
You are now prompted to select whether a purge is required
Selecting N here enables you to bypass the next two displays
Pre purge activates relay 3 for the amount of time specified
before the heat relay is activated.
Post purge will activate relay 3 for the amount of time specified
before the heat relay is activated.
DOUBLE IGNITION
Enabling this option gives the following functionality.
When the heat relay is activated for the first time of each switching time, it will switch off after 30 seconds.
Then after a further 10 seconds the relay is re-energised and will operate as normal.
This operates at the start of every switching period and is used to
ensure that the heater fires when installed in areas where there is
a high level of condensation.
If post purge is enabled, the fan will timeout before the heater re-fires.
PROVING SWITCH
You are now prompted to select whether you have a proving switch
on the system.
When there is a demand for heat, the Energymizor looks to check firstly that the proving switch is not made.
Relay 3 is then energised giving pre-purge if required. The proving switch then makes followed by relay 2
being energised.
When you have completed the configuration procedure you will be returned to the setup menu screen. At
this point you can press RUN to return to the Normal RUN mode or you can continue to program the other
settings by selecting another menu option.
UP/DOWN TEMPERATURE LIMIT
You are now prompted to enter the limit for the Up/Down temperature
keys. With a limit set to 02, you can increase/decrease the set
temperature by 2°C

ENERGYMIZOR 2 ONLY

10
ENTER MODULATION
DIFFERENTIAL: 04
PURGE REQUIRED
N<0> Y<1> : 1
PREPURGE TIME
<MINS> : 00
POST PURGE TIME
<MINS> :00
DOUBLE IGNITION
N<0> Y<1> :0
PROVING SWITCH?
N<0> Y<1> :0
USER TEMP LIMIT
TEMP: 00°C