The components that make up the gas
flue evacuation system must be de-
clared suitable for the specific operat-
ing conditions and provided with CE
marking.
It is mandatory to create a first vertical
section measuring at least 1.5 meters to
guarantee correct expulsion of the flue
gases.
It is advisable to make a maximum of 3 direction
changes, in addition to that resulting from the
rear connection of the appliance to the chimney,
using 45 ­ 90 ° bends or Tee fittings (Fig. 11).
Always use a Tee fitting with inspection cap at
each horizontal and vertical change of the gas
flue path (B - Fig. 11).
B
On the first tee, at the gas flue outlet of the ap­
pliance, a pipe must be connected at the bottom
for the evacuation of any condensation that may
form in the chimney (Fig. 12).
40
B
B
Fig. 11
The horizontal sections must have a maximum
length of 2­3 m with an upward incline of 3­5%
(Fig. 11).
Anchor the pipes with suitable collars to the wall.
The flue gas fitting MUST NOT BE connected:
• to a chimney used by other generators (boilers,
stoves, fireplaces, etc. ...);
• to air extraction systems (hoods, vents etc. ...)
even if "ducted".
It is forbidden to install shut­off and draught
valves.
The exhaust of the combustion products must
be provided on the roof.
5.6 Roof exhaust with traditional
fireplace
The chimney for the evacuation of flue gases
must be made by qualified personnel in compli­
ance with standards UNI 10683­ EN 1856­1­2­ EN
1857­EN 1443­ EN 13384­1­3­ EN 12391­1 both in
terms of the dimensions and the materials used
in its construction.
The evacuation of flue gases via a traditional
chimney (Fig. 13) can be done as long as you are
sure of the state of maintenance of the chimney.
In the case of an old chimney, it is advisable to
renew it using ducting.