RHOSS Mini-Y Serie Gebrauchsanweisung Seite 63

Elektronische steuerungen
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 94
Code
Rearm
040
Automatic
041
Automatic
042
Automatic
043
Automatic
044
Automatic
045
Manual
046
Automatic
Automatic
050
055
Automatic
056
Manual
Automatic
Automatic
Automatic
057
Automatic
Automatic
Automatic
060
Automatic
Automatic – M anual
(restricted by the
099
number of inter ventions
set)
100
101
Manual
102
Manual
103
Manual
104
Manual
105
Manual
106
Manual
107
Manual
108
Automatic
110
Automatic
111
Manual
112
Manual
113
Manual
Delay
0 s
0 s
0 s
0 s
0 s
Can be set from
compressor start-up
0 s
Can be set on mac hine
start-up i n normal
conditi ons
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
0 s
120 s
0 s
Can be set by par ameter
Can be set by par ameter
Can be set by par ameter
Can be set by par ameter
Can be set by par ameter
Can be set by par ameter
Can be set by par ameter
Can be set by par ameter
0 s
0 s
0 s
Notes
Maxi mum functioning hours limit r eached signal
Maxi mum functioning hours limit r eached signal
Maxi mum functioning hours limit r eached signal
Maxi mum functioning hours limit r eached signal
Maxi mum functioning hours limit r eached signal
It must be deacti vated for the entire duration of the defrosti ng cycl e or, if acti ve,
the heat rec over y unit
Maxi mum functioning hours limit r eached signal
Insufficient water in the storage tank signal
Clock board not c onnected or impossibl e to memorise data in the alar ms log
The rearm of the alarm is restricted by a fi xed hysteresis of 5.0 Volts
The rearm of the alarm is restricted by a fi xed hysteresis of 5.0 Volts
The rearm of the alarm is restricted by a fi xed hysteresis of 5.0 Volts
The rearm of the alarm is restricted by a fi xed hysteresis of 5.0 Volts
The rearm of the alarm is restricted by a fi xed hysteresis of 5.0 Volts
The rearm of the alarm is restricted by a fi xed hysteresis of 5.0 Volts
Recover y unit management high temperatur e alar m
After 3 recovery attempts by the pCOe, it bec omes manual rearm. The
compressors in the sec ond circuit ar e stopped from the first signal.
63
ALARM SIGNAL S