W inter CS chart in Shifting logic
53
50
46
42
38
34
30
4
6
8
10
Example:
With a minimum Set-point of 30°C and a maxi mum Set-point of 53°C,
with an external analogue signal equal to 15 mA, a worki ng Set-point of
46°C is s et.
T
Operati ve Set-poi nt
S
External analogue signal (4÷20 mA)
Summer CS chart in Offset logic
3
2
1
0
-1
-2
-3
4
6
8
10
Example:
With a minimum Offs et of -3°C and a maximum Offs et of 3°C, with an
external analogue signal equal to 8 mA, the Set-point s et is decreased
by 1.5°C.
W inter CS chart in Offset logic
3
2
1
0
-1
-2
-3
4
6
8
10
Example:
With a minimum Offs et of -3°C and a maximum Offs et of 3°C, with an
external analogue signal equal to 16 mA, the Set-point set is increas ed
by 1.5°C.
T
Variation with res pect to the Set-point s et
S
External analogue signal (4÷20 mA)
12
14
16
18
20
S (mA)
12
14
16
18
20
S (mA)
12
14
16
18
20
S (mA)
I.1.11 Set-point Compensation
The Set-point c ompensati on func tion on the basis of the outdoor
temperature c arries out the algebra s um between the Set-point value
set and an offs et value calcul ated depending on the temperature of the
outdoor air. It is possibl e to decide whether to acti vate the func tion in
both functioning modes (summer/winter) or onl y in one.
This func tion is not availabl e if the Scrolling Set-point (CS) functi on is
enabled.
Press the Prg key for 2 s econds to access it.
Press the MODE key until the following mas ks are displ ayed:
MODE
ALARM
Prg
ON/OFF
MODE
ALARM
Prg
ON/OFF
Press the Prg key for 2 seconds .
Modify the Y parameter ( yes) to enable the function.
Press the MODE and ON/OFF keys at the s ame ti me to memorise the
val ue s et.
For setting in winter mode, proceed as i ndicated for the s ummer mode.
To return to the initial screen, press the MODE and ON/OFF keys at the
same time.
I.1.12 Integrativ e resistance (KRIT)
The el ectric resistance (KRIT access ory) acts as integration i n winter
mode (onl y on machi ne i n heat pump mode). If enabl ed, this func tion
allows to manage the integrative resistance. The integrative resistance
can be managed on the basis of the outdoor air temperature. In this
case the presence of a probe is necess ary (KEAP acc essor y).
The integrative resistanc e function based on the temperature of the
outdoor air is not available if the Scrolling Set-point (CS) functi on is
enabled.
39
CONTROL PANELL PST
MODE
ALARM
Prg
ON/OFF
Enabling of c ompensati on func tion of
the Set-point in Summer mode.
Enabling of c ompensati on func tion of
the Set-point in Winter mode.
MODE
ALARM
Prg
ON/OFF

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Verwandte Produkte für RHOSS Mini-Y Serie

Inhaltsverzeichnis