Press the MODE key until the following mas ks are displ ayed:
MODE
ALARM
Prg
ON/OFF
MODE
ALARM
Prg
ON/OFF
To set the Set-poi nts, proceed as indicated for the indi vidual Set-poi nt
(see I.5.8).
To return to the initial screen, press the MODE and ON/OFF keys at the
same time.
I.1.10 Scrolling Set-point
The CS access ory (scrolling Set-poi nt, vi a 4÷20 mA external analogue
signal by installer) can assume two func tioni ng logics (factor y set
according to request):
"Shifting Set-point" logic;
"Offset Set-point" logic.
In the Shifting Set-point l ogic, the analogue signal (opportunely
configured) s ets the Set- point at which the machine must operate
directly (the Set-point set on the c ontrol panel is bloc ked).
In the Offset Set-poi nt logic, the analogue signal (opportunel y
configured) c orrects the Set-point set on the control panel.
Press the Prg key for 2 s econds to access it.
If the CS access ory is enabl ed, press the MODE key until the following
mas ks are displayed:
MODE
ALARM
Prg
ON/OFF
MODE
ALARM
Prg
ON/OFF
NOTE: Depending whether Shifti ng or Offs et mode has been s et; the
followi ng settings refer to the res pecti ve modes.
To set the Shifting Set-poi nt in s ummer mode, pr oceed as follows:
Press the Prg key for 2 s econds to access it.
Summer double Set-point (°C)
Winter double Set-point (°C)
MODE
ALARM
Prg
ON/OFF
Scrolling Set-poi nt in Summer mode
Scrolling Set-poi nt in Winter mode
MODE
ALARM
Prg
ON/OFF
The followi ng mas ks are displayed:
MODE
ALARM
Prg
ON/OFF
MODE
ALARM
Prg
ON/OFF
To set the Set-poi nts, proceed as indicated for the indi vidual Set-poi nt
(see I.5.8).
To set the Shifting Set-poi nt in winter mode, proceed as follows:
Press the Prg key for 2 seconds .
The followi ng mas ks are displayed:
MODE
ALARM
Prg
ON/OFF
MODE
ALARM
Prg
ON/OFF
To set the Set-poi nts, proceed as indicated for the indi vidual Set-poi nt
(see I.5.8).
To return to the initial screen, press the MODE and ON/OFF keys at the
same time.
Summer CS chart in Shifting logic
16
14
12
10
8
6
4
4
6
Example:
With a minimum Set-point of 4°C and a maximum Set- point of 16°C,
with an external analogue signal equal to 12 mA, a worki ng Set-point of
10°C is s et.
38
CONTROL PANELL PST
Scrolling summer Set-point fi eld of
variation s etti ng: Minimum Set-point
or mini mum offset.
Scrolling summer Set-point fi eld of
variation s etti ng: Maximum Set-point
or maxi mum offs et.
MODE
ALARM
Prg
ON/OFF
Scrolling winter Set- point field of
variation s etti ng Minimum Set-poi nt or
minimum offset.
Scrolling winter Set- point field of
variation s etti ng Maxi mum Set-point
or maxi mum offs et.
8
10
12
14
16
18
20
S (mA)