Herunterladen Inhalt Inhalt Diese Seite drucken

Wrong Wiring (Error Code 5) - Weidmuller 8808420000 Bedienungsanleitung

Ie-ct kabel- und installationstester
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5.10 Wrong Wiring (Error Code 5)

If the IE-CT detects wrong termintated conductors in an installation or cable the conductor LED (F) for
the respective conductors always light in pairs. The conductor LED for the terminal pole at the near end
of the installation line lights continuously, the conductor LED for the terminal pole at the far end is
flashing.
IE-CT
Mainframe
In our example two errors are detected:
1. Wrong wiring (error code 5), conductor LED 5 lights continuously and conductor LED 6 flashes.
2. Wrong wiring (error code 5), conductor LED 6 lights continuously and conductor LED 5 flashes.
The error code for wrong wiring is digit 5.
Note
The near end of an installation line is the terminated side that the IE-CT Mainframe is connected
to. The far end of an installation line is the terminated side the IE-CT Test Box is connected to.
near end of
Installation line
Installation line
23
far end of
IE-CT
Installation line
Test Box