Verfügbare Sprachen

5.3 Switch on and Test

Terminate IE-CT Mainframe and IE-CT Test Box, then start the installation test and line identification as
shown below.
%
Press the Start Key (D) to turn on the
IE-CT Mainframe.
#
During the test run, the green LED (G) flashes. The
test is finished when the green LED stops flashing.
$
The green LED (G) lights without interruption if no
errors were detected, the installation is OK.
Press the Error Key (H) to get the number of the
connected Test Box. This number is shown as a
flashing digit in the numeric display (B).
!
If installation errors are detected the conductor
LED (F) of the respective poles will light red and
the error code digit lights in the numeric display
(B).
"
If more than one installation error is detected,
press the Step Key (H) to display the other errors.
20
press Start Key
The green LED flashes
The green LED flashes
without interruption, no
errors were detected
Example: interruption
(error code 3) of wires
1, 2, and 3.
press Step Key