Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data; Operating Parameters - Dräger Safety Barrier Zone 2 Gebrauchsanweisung

Sicherheitsbarriere
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1

Technical data

3.2
Wiring diagram
HAZARD AREA
Bay unit
3A
+24V
4A
4 - 20 mA
+24 V
3B
4 - 20 mA
4B
+24 V
3C
4 - 20 mA
4C
+24 V
3D
4 - 20 mA
4D
3.3
Installing the safety barrier
Mount the safety barrier on the top.hat rail. Then install the wiring as
shown in the wiring diagram.
10
SAFE AREA
Central Unit
+
0 V
Safety Barrier
1A
U
2A
4 - 20 mA
1B
U
2B
4 - 20 mA
1C
U
2C
4 - 20 mA
1D
U
2D
4 - 20 mA
PA
00233410_en.eps
4
Technical data
4.1
Ex parameters
U
m
Max. output current I
o
Max. output voltage U
o
Max. output power P
o
Gas group
Max. connectable capacity C
o
Max. connectable inductance L
o
Max. inductance resistance
L
o
------
ratio
:
R
o
Connection parameters are not valid for circuits (except for lines)
which contain both inductance and capacities.
4.2

Operating parameters

Operating voltage U
B
Ambient temperature T
amb
Max. load R
Bmax
Max. cable cross section Q
max
Series resistance R
s
Protection class
250 V
93 mA
28 V
660 mW
IIC
IIB
IIA
83 nF
650 nF
2150 nF
4 mH
16 mH
32 mH
H
H
------- -
------- -
54
217
435
24 V ± 1.2 V
0 - 60 °C
250 Ω
2
2,5 mm
300 Ω
IP 20
Safety Barrier Zone 2
H
------- -

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis