Over-current protection.
A load output over-current or short-circuit is indicated by a flashing
load icon. The controller will disable the load output and try to re-
enable after 30 seconds.
Shut down after 60s in case of 110%-130% load.
Shut down after 5s in case of 130%-160% load.
Short circuit protection
In case of a short circuit the controller will switch off the load output
and wait for 30s and then try to restart.
USB voltage high.
Disconnect the USB load. If the alarm persists the USB output is
defect.
Wiring error or short circuit in the charge controller
Wiring error: the minus of the solar panel is connected to
the minus of the battery.
Internal defect.
Open circuit in the charge controller
Internal defect.
Open circuit in the load output circuit
Internal defect.
Wiring error or short circuit in the load output circuit
Wiring error: the minus of the load and the minus of the
battery are interconnected.
Internal defect.