Now proceed with connection of the differential
pressure switch to connections P3 and P4
6
" V1 " currently flashes on the control display;
use the TOUCH PAD
confirm by pressing enter.
Carry out the procedure described above for V1
also for fan V2.
When fan V2 has been set as well, go back to the
main screen by pressing "M"
Disconnect the differential pressure gauge and put
the rubber caps and the cover of the front panel
back in place.
+
to select fan " V2 " and
_
3 times.
AUTOMATIC CALIBRATION
o
a
nly with
utomatic flow rate control
system installed
1. Turn on the appliance
by pressing the ON/OFF key on the display.
2. Press the ON/OFF and "M" Menu keys at the same
time to access the TECHNICAL MENU.
3. Use the TOUCH PAD to select the installer menu
.
Press the Enter key to confirm
Select the "V" symbol and confirm
The message V1 flashes;
Perform the setting of the fan V1;
access the menu by pressing enter, the display shows:
V V
V V
Press the Enter key to confirm
English
.
.
set the nominal design
flow rate (m
/h) using
3
+
the TOUCH PAD
.
_
.
77