Condensate drain connection
Position the condensate drain based on the desired
connection:
Unscrew the plug and fix a drain or siphon as
indicated in the figure.
Condensate must be drained from a minimum
height of 100 mm.
If you choose the version with right side connection,
swap the plug of the condensate drain.
standard
connection
Y
SETTING THE FLOW RATES
Before setting flowrates, fans are run at factory default
speed.
Before setting flowrates, Touch Pad is inithbited to
perform any speed modulation. This is communicated
by the message "Tab" blinking in the central field of
the display.
WARNING!: no speed regulation is possible without
first flowrate setting
DAY
°C
To set the air flow rate based on the number of fan
revolutions, there are two possible types of calibration:
STANDARD CALIBRATION
In the absence of the Flow Rate Automatic
Control System.
AUTOMATIC CALIBRATION
If there is the Automatic Flow Rate Control
System.
STANDARD CALIBRATION
– l
s
eft
ide
1. Use a screwdriver to remove the front panel cover.
2
3
2. Remove the rubber caps of the connections P1 and P2
relative to fan V1.
c
onfiguration
1
English
75