Conventional aspiration smoke detector
2.
3.
4.
Fire source identification
Fire source identification is set using the FAS‑ASD‑DIAG Diagnostic Software via the
ROOM·IDENT screen.
1.
2.
3.
4.
5.
6.
7.
8.
6

Technical data

Electrical
Power supply
(Conventional)
Current consumption
from auxiliary power
supply (24 V)
Mechanical components
LEDs on FCS-320-TM
Bosch Sicherheitssysteme GmbH
Replug the X4 jumper when inserting the detection module (PIN 1-2 or PIN 2-3, or vice
versa). Replugging will cause airflow calibration to be carried out automatically.
The green operation display flashes when the FCS-320-TM is initializing. If initialization is
complete, the operation display lights up permanently.
The airflow of the FCS-320-TM must not be influenced during the initialization phase.
Click the [Train] button. This opens the view with adjustable values used to determine
the transport times for fire source identification in areas A-E.
First enter the number of air sampling openings.
Then enter the blowing out time and voltage of the blowing out and aspiration fan.
You can access the Help function by clicking the question mark to the right of the relevant
setting.
Click the appropriate aspiration point (A-E) for which the transport time is to be
determined.
Enter the preselection time necessary to reach the aspiration point and supply the smoke.
Once the selected preselection time has expired, the appropriate smoke aspiration point
must be charged with smoke. Once the preselection time has expired, the smoke must be
available at the aspiration point for another 10 to 15 seconds.
Using the smoke level, check that there is no smoke in the aspiration pipe.
Click the [Start] button. The FCS-320-TM-R switches to the aspiration pipe blowing out.
The display of the aspiration point concerned is yellow.
Once the preselection time has expired, switch the FCS-320-TM-R to aspiration. The
smoke must now be available at the selected aspiration point. The smoke level will
display if smoke is detected by the FCS-320-TM-R . The display of the selected aspiration
point turns green and the determined time is entered. Teaching mode for the selected
aspiration point is exited.
14 V DC-30 V DC
Fan voltage
9 V
Starting current
120 mA
In standby
90 mA
At alarm
125 mA
Operation
Malfunction
Alarm
Quick installation guide
10.5 V
12 V
130 mA
145 mA
110 mA
130 mA
135 mA
150 mA
Green LED
Yellow LED
1 red LED for main alarm
Technical data | en
19
13.5 V
160 mA
150 mA
175 mA
2020.04 | 2.0 | F.01U.123.590