Herunterladen Inhalt Inhalt Diese Seite drucken

Product Description; Technical Data - Bosch FAA-500 Installationsanleitung

Vorschau ausblenden Andere Handbücher für FAA-500:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 4
FAA-500 | FAA-500-R

Product Description

See Figure 1, Page 3 and Figure 2, Page 3.
Position Description
1
Fire panel
2
External Detector Alarm Display
(MPA; not for relay bases)
3
Next detector
4
Holders for cable ties
5
Lettering for LSN connection
* For concrete and wooden ceilings, replace with FAA-500-SPRING (part nr. F.01U510.028, delivery unit 10 pcs.,
red marking).
Wiring
See Figure 1, Page 3 and Figure 2, Page 3.
Wire the LSN bases according to the lettering for LSN connection (5).
NOTICE!
During cabling, the holders for cable ties (4) can be used to fix the base.
Terminals
0V | +V *
a1/a2
b1 | b2
c
NO | NC | COM
* Terminals for interconnecting all bases with voltage supply for other LSN elements.
Mounting
See Figure 2, Page 3.
Install the LSN base only together with the FAA-500-BB Ceiling Mount Back Box or with FAA-500-SB-H Surface Mount
Back Box.
Ensure an even arrangement of boxes and bases. This allows parallel alignment of the detectors oblong, middle
windows for a harmonious total optical impression.
1.
Installation with a FAA-500-BB Ceiling Mount Back Box: Place the base in the ceiling mount back box so that the
triangular mark (7) on the outer rim of the back box matches with the single guideway (8).
Installation with a FAA-500-SB-H Surface Mount Back Box: Ensure the correct alignment of the base.
2.
Turn the base until the fastening screws are in the middle of the long slit (6).
3.
Slightly turn each base until the bases align in one direction.
4.
Tighten the four screws.

Technical Data

Current consumption
Contact load
Wire gauge
Product ID
Bosch Sicherheitssysteme GmbH
Position Description
6
7
8
9
Function
Voltage - | Voltage +
LSN a in/out
LSN b in | LSN b out
Indicator output
Shielding
Relay (FAA-500-R)
Long slit
Triangular mark (ceiling mount back box)
Single guideway
Spring for detector mounting in false ceiling panels *
Wire
black (bk) | red (rd)
white (wh)
yellow (ye) | yellow (ye)
green (gn)
FAA-500
-
-
2
2
0.3 mm
- 3.3 mm
(22 AWG - 12 AWG)
4.998.15.297
en
5
FAA-500-R
0.2 mA
1 A, 30 V DC
4.998.15.299
F.01U.000.615 | 3.0 | 2011.06