4.4.5 Voltage sense (connection terminal G, see appendix A)
For compensating possible cable losses during charging, tw o sense wires can be connected with which the voltage directly on the
battery or on the positive and negative distribution points can be measured. Use w ire w ith a cross-section of 0,75mm².
During battery charging, the Quattro w ill compensate the voltage drop over the DC cables up to a maximum of 1 Volt (i.e. 1V over the
positive connection and 1V over the negative connection). If the voltage drop threatens to become larger than 1V, the charging current
is limited in such a w ay that the voltage drop remains limited to 1V.
4.4.6 Tem perature sensor (connection terminal G, see appendix A)
For temperature-compensated charging, the temperature sensor (supplied w ith the Quattro) can be connected. The sensor is isolated
and must be fitted to the negative terminal of the battery.
4.4.7 Parallel Connection
Up to six identical units can be connected in parallel. When connecting MultiPlus-II units in parallel, the follow ing requirements must be
met:
All units must be connected to the same battery
A maximum of six units connected in parallel.
Only identical devices may be connected in parallel.
The DC connection cables to the devices must be of equal length and cross-section.
If a positive and a negative DC distribution point is used, the cross-section of the connection between the batteries and the DC
distribution point must at least equal the sum of the required cross-sections of the connections between the distribution point and
the MultiPlus-II units.
Place the MultiPlus-II units close to each other, but allow at least 10cm for ventilation purposes under, above and beside the units.
It is essential the negative battery terminal betw een the units is alw ays connected. A fuse or circuit breaker is not allow ed.
UTP cables must be connected directly from one unit to the other (and to the remote panel). Connection or splitter boxes are not
permitted.
Alw ays interconnect the negative battery cables before placing the UTP cables.
Only one remote control means (panel or sw itch) can be connected to the system.
4.4.8 Three-phase operation
The MultiPlus-II can also be used in 3-phase w ye (Y) configuration. To this end, a connection betw een the devices is made by means of
standard RJ45 UTP cables (the same as for parallel operation). The system (MultiPlus-II plus an optional control panel) w ill require
subsequently configuration (see Section 5).
Pre-requisites: see Section 4.4.5.
1.
Note: the MultiPlus-II is not suitable for 3-phase delta (Δ) configuration.
2.
When the AS4777.2 grid code has been selected in VEConfigure, only 2 units in parallel per phase are allow ed in a three
phase system.