Product Information / Produktinformation A6824 / A6824R
Gateway Card
1.5

Installation and Mounting

A prepared 3U slot in a 19" rack, or other Intermas−compatible enclosure, is required for
mounting the A6824 / A6824R gateway.
For use of the A6824R the slot must be fitted with a 30−pin plug connector (DIN 41612/
IEC60603 design C/3). The pin assignment is listed in the following table.
1
not used
2
UB+ (+ 24V)
3
must be blank
4
RS 485 Bus 1 A
5
RS 485 Bus 2 A
6
RS 485 Bus 3 A
7
RS 485 Bus 4 A
8
RS 485 Bus 5 A
9
RS 485 Bus 6 A
10
Modbus RTU A
For use of the A6824 the slot must be fitted with a 48−pin plug connector (DIN 41612, design
F 48 M). The pin assignment is listed in the following table.
2
UB+ (+ 24V)
4
RS 485 Bus 1 A
6
not used
8
not used
10
not used
12
RS 485 Bus 2 A
14
RS 485 Bus 3 A
16
RS 485 Bus 4 A
18
RS 485 Bus 5 A
20
RS 485 Bus 6 A
22
Modbus RTU A
24
not used
26
not used
28
not used
30
not used
32
not used
a
not used
U− (0V/Common)
not used
RS 485 Bus 1 GND
RS 485 Bus 2 GND
RS 485 Bus 3 GND
RS 485 Bus 4 GND
RS 485 Bus 5 GND
RS 485 Bus 6 GND
Modbus RTU GND
d
U− (0V/Common)
RS 485 Bus 1 GND
not used
not used
not used
RS 485 Bus 2 GND
RS 485 Bus 3 GND
RS 485 Bus 4 GND
RS 485 Bus 5 GND
RS 485 Bus 6 GND
Modbus RTU GND
not used
not used
not used
not used
not used
b
not used
UN+ (+24V redundant)
not used
RS 485 BUS 1 B
RS 485 BUS 2 B
RS 485 BUS 3 B
RS 485 BUS 4 B
RS 485 BUS 5 B
RS 485 BUS 6 B
Modbus RTU B
b
UN+ (+24V redundant)
RS 485 BUS 1 B
not used
not used
not used
RS 485 BUS 2 B
RS 485 BUS 3 B
RS 485 BUS 4 B
RS 485 BUS 5 B
RS 485 BUS 6 B
Modbus RTU B
not used.
not used
not used
not used
not used
Page 10
c
1
2
3
4
5
6
7
8
9
10
z
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32