Supported Modbus commands
Function
Description
Data format code
01
Read Coil
02
Read Input
03
Read Holding Registers 16-bit integer value
04
Read Input Registers
Coil Status (01)
Address
Description
0
1=On, 0=Off
Start and stop of motor
1
1=Reset alarm,
0=normal
1 is automatically changed
2
Not in use
Default 0, must not be changed
3
0=ClockWise,
1=CounterClockWise
Input Status (02)
Address
Description
0
1=Rotation alarm,
0=normal
signal from rotation guard
(rotation guard is always active
1
1=Low voltage alarm,
0=normal
2
1=High voltage alarm,
0=normal
3
1=High current alarm,
0=normal
4
1=Temperature alarm,
0=normal
5
Not in use
6
Not in use
7
Not in use
8
Alternates
Each pulse from rotation
between 0 and 1
9
Not in use
SERVICE AND MAINTENANCE
No batteries, service or maintenance are required.
Please contact your supplier if faults arise.

TROUBLESHOOTING

LED fault indication
No light: Lacking 230 V supply voltage or
defective RHX2M.
Red light: General alarm, motor is stopped
until alarm situation is no longer present.
Red flash: Rotation guard alarm, no pulses
detected.
Alarms
Alarm relay terminals 4 and 6 are activated in
alarm situations or if the 230 V power supply is
lacking.
General alarm
Can be activated by high/low voltage, high cur-
rent or high temperature. General alarms are au-
tomatically reset once the alarm situation is no
longer present. General alarms triggered by high
current (short-circuited motor) are not reset au-
tomatically.
General alarms can also be reset by short-cir-
cuiting the rotation guard terminals (10-11) for
five seconds or via Modbus.
Rotation guard alarm
The rotation guard input is monitored whenever
the RHX2M controller starts the motor. If no
pulse is received before the motor has rotated
50 times, motor speed is reduced to 0 rpm.
Speed is then gradually increased again until
the speed setting is reached. If once again no
pulse is received, this sequence is repeated
three times in all before the rotation guard alarm
is activated.
10
Rotation guard alarms can be reset by short-cir-
cuiting the rotation guard terminals (10-11) for
at least 1 second or via a Modbus command.
Status 1-bit value
Rotation guard alarms are typically caused by
Status 1-bit value
defective drive belt or incorrect rotor torque (see
"Motor is noisy"), a problem that occurs most
16-bit integer value
often at max. air quantity through the rotor.
Motor is noisy and runs unstably
Remarks
Motor type
The DIP switches for selecting motor type are
Resets alarms when
incorrectly set (see fig. 2) or the wrong step
changed from 0 to 1
motor is installed.
back to 0 after 1.5 s
Rotor adjustment
Rotor turns sluggishly and step motor is over-
Determines motor
loaded.
rotation direction
When rotary heat exchangers/ventilation units
are installed correctly, the rotor should turn eas-
Remarks
ily when pushed by hand. If incorrectly installed,
Alarm due to lacking
the torque required to turn the rotor may in-
crease dramatically because:
The ventilation unit is not level
with Modbus control)
Rotor adjustment is lacking/incorrect
Alarm due to low
Sealing strips and brushes are too tight
If the step motor is overloaded, it loses syn-
230 V supply voltage
chronisation and produces a lower pulsating
Alarm due to high
torque. As a result, it runs "jerkily", is noisy and
230 V supply voltage
does not rotate correctly. This damages neither
Alarm due to high
the motor nor the controller, however.
current in motor
Once the rotor has been correctly adjusted and
is capable of being turned at normal torque, the
Alarm due to high
motor can be restarted and will rotate normally.
temperature inside
RHX2M controller
DISPOSAL AND ENVIRONMENTAL
PROTECTION
Help protect the environment by disposing of
the packaging and redundant products in a re-
sponsible manner.
guard changes value
Product disposal
OJ ELECTRONICS A/S
Stenager 13B · DK-6400 Sønderborg
Tel. +45 73 12 13 14 · Fax +45 73 12 13 13
oj@ojelectronics.com · www.ojelectronics.com
CE MARKING
OJ Electronics A/S hereby declares that the
product is manufactured in accordance with
Council Directive 92/31/EEC on electromagnetic
compatibility (and subsequent amendments)
and Council Directive 73/23/EEC on electrical
equipment designed for use within certain volt-
age limits (and subsequent amendments).
Applied standards
EN 61000-6-2 and EN 61000-6-3 Electromag-
netic compatibility (EMC)
EN 60947-4-3:2001 Low-voltage switchgear
and controlgear (LVD)
The product is designed to be incorporated in
machinery or to be combined with other ma-
chine components for incorporation in machin-
ery covered by Directive 98/37/EEC of the
European Parliament and of the Council (and
subsequent amendments). The product itself
therefore does not comply with the require-
ments of this directive in all respects.
ABBILDUNGEN
Folgende Abbildungen finden sich ganz hinten
in der Anweisung:
Products marked with this symbol
must not be disposed of along with
household refuse but must be delivered
to a waste collection centre in accor-
dance with current local regulations.
Deutsch
© 2011 OJ Electronics A/S
Abb. 1: Physische Abmessungen der Schritt-
motorsteuerung
Abb. 2: Elektrische Anschlüsse
Abb. 3: Montage des Drehwächters
Abb. 4: Physische Abmessungen des Schritt-
motors
Abb. 5: Beispiel für einen Befestigungsbeschlag
Abb. 6: Motorriemenscheibe für max. Moment
Abb. 7: Motorriemenscheibe für weniger Vari-
anten
Abb. 8: 0-10V-Steuerung
Abb. 9: Kompensation für nichtlineare Wärme-
übertragung
Abb. 10 Modbus Anschlüsse
Abb. 11: Elektrische Anschlüsse Rotorguard
ALLGEMEINE ANGABEN
RHX2M ist eine Schrittmotorsteuerung, ausge-
legt für eine präzise und geräuscharme Steue-
rung von rotierenden Wärmetauschern in
Lüftungsaggregaten.
Die Steuerung besteht aus einer Schrittmotor-
steuerung, einem Schrittmotor und einem Dreh-
wächter. Der Drehwächter dient zur
Überwachung, ob der Rotor sich entsprechend
dreht.
RHX2M sorgt für eine äußerst genaue Regelung
der Rotordrehzahl, was eine energieoptimierte
Wärmerückgewinnung möglich macht.
PRODUKTPROGRAMM
Typ
Produkt
RHX2M-1212
VVX-Steuerung und Motor
Modbus
RHX2M-1412
VVX-Steuerung und Motor
Modbus
RHX2M-1612
VVX-Steuerung und Motor
Modbus
FUNKTION
RHX2M-1x12 lässt sich mit Vorteil als Ersatz für
herkömmliche Getriebemotorlösungen einset-
zen. Der Schrittmotor verfügt im gesamten
Drehzahlbereich über ein gleichmäßiges Mo-
ment, im Unterschied zu Getriebemotoren, die
bei niedrigen bzw. hohen Drehzahlen Moment
verlieren. Die konstante Momentkennlinie des
Schrittmotors ermöglicht einen wesentlich grö-
ßeren Arbeitsbereich, in dem sich die Rotor-
drehzahlen präzise regeln lassen. Damit ist eine
energieoptimierte Steuerung der Wärmerückge-
winnung möglich, und lassen sich genauere
Temperaturen erzielen.
RHX2M lässt sich entweder mit einem 0-10V-
Signal oder über Modbus steuern, und eignet
sich daher sowohl für die Kopplung an eine her-
kömmliche Lüftungsautomatik als auch für mo-
dernere Lösungen, wie z. B. OJ Air2 von
OJ Electronics.
Der Schrittmotor wird in Mikroschritten mit si-
nusförmigen Konstantstromsignalen gesteuert,
um eine Motorwellenrotation mit gleichmäßigem
Moment im gesamten Drehbereich zu gewähr-
leisten. Hiermit werden Momentimpulse vermie-
den und ein geräuscharmer Betrieb erreicht.
VERBOT DER INBETRIEBNAHME
Eine Inbetriebnahme ist so lange ausdrücklich
verboten, bis die Maschine/das Produkt, in
die/das oben erwähnte Produkt eingebaut wird,
insgesamt als in Übereinstimmung mit allen re-
levanten Bestimmungen der Maschinenrichtlinie
98/37/EWG sowie der nationalen Gesetzge-
bung, z.B. Bekanntmachungen der Gewerbe-
aufsicht erklärt wurde.
Das Produkt darf erst unter Spannung gesetzt
werden, wenn die gesamte Installation die An-
forderungen ALLER relevanten EU-Richtlinien
einhält.
Ist das Produkt gemäß dieser Installationsanlei-
2 Nm
0-10 V DC IP54
4 Nm
0-10 V DC IP54
6 Nm
0-10 V DC IP54

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Rhx2m-1212Rhx2m-1412Rhx2m-1612

Inhaltsverzeichnis