Herunterladen Inhalt Inhalt Diese Seite drucken

Carrier 42QSS009DS Installationshandbuch Seite 20

Vorschau ausblenden Andere Handbücher für 42QSS009DS:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 29
5. WIRING
Model(Btu/h)
Phase
Frequency and volt
Indoor
Rated Current
Fuse Rating(Field Supply)
Power Cord(Field Supply)
Phase
Frequency and volt
Outdoor
Rated Current
Circuit Breaker(Field Supply)
Power Cord(Field Supply)
Indoor/outdoor connecting wiring
(Field Supply)
CAUTION
Separate the low voltage wiring (signal wire) and high voltage wiring (power supply wiring) at least 0.5m
so that they do not pass through the same place together. Proximity may cause electrical interference,
malfunctions, and breakage.
NOTE OF FUSE SPECIFICATIONS:
(applicalbe to units adpot R32 refrigerant only, and the fuse is made of ceramic.)
1. The specification of outdoor unit fuse is T20A/250VAC(for <24000Btu/h unit), T30A/250VAC(for
>24000Btu/h unit )
2. The specification of indoor unit fuse is T5A/250VAC, T10A/250VAC.
GB-19
36k(3N)
48k(3N)
1-Phase
1-Phase
220-240V~ 50Hz
2.0A
10A
H05VV-F;
H05VV-F;
3×1.0mm
2
3×1.0mm
3-Phase
3-Phase
380-415V 3N~ 50Hz
10.0A
25A
H07RN-F;
H07RN-F;
2
5×2.5mm
5×2.5mm
Shielded wire;
Shielded wire;
2×0.2mm
2
2×0.2mm
60k(3N)
1-Phase
2.0A
2.0A
10A
10A
H05VV-F;
2
3×1.0mm
3-Phase
14.0A
13.0A
32A
32A
H07RN-F;
2
5×2.5mm
Shielded wire;
2
2×0.2mm
2
2
2

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis