Eaton PowerXL DG1 VFD Serie Montageanweisung Seite 18

Vorschau ausblenden Andere Handbücher für PowerXL DG1 VFD Serie:

Werbung

Instruction Leaflet IL040016EN
Effective March 2014
Factory-Set Control Terminal Functions
I/O Connection
Pin
Signal Name Signal
1
+10V
2
AI1+
3
AI1–
4
AI2+
i
5
AI2–
6
GND
7
DIN5
8
DIN6
9
DIN7
10
DIN8
11
CMB
12
GND
13
24V
14
DO1
15
24Vo
16
GND
17
AO1+
18
AO2+
19
24Vi
20
DIN1
21
DIN2
22
DIN3
23
DIN4
24
CMA
25
A
26
B
27
R3NO
28
R1NC
29
R1CM
30
R1NO
31
R3CM
32
R2NC
33
R2CM
34
R2NO
EATON
18
www.eaton.com
SW1
AI1 0–10V
AI2 0–20 mA
AI2 SW1
AI2 SW2
SW2
On
(RS-485 matching resistor)
Off
Ref. Output Voltage
Analog Input 1
Analog Input 1 Ground
Analog Input 2
Analog Input 2 Ground
I/O Signal Ground
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
DI5 to DI8 Common
I/O Signal Ground
+24 Vdc Output
Digital Output 1
+24 Vdc Output
I/O Signal Ground
Analog Output 1
Analog Output 2
+24 Vdc Input
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
DI1 to DI4 Common
RS-485 Signal A
RS-485 Signal B
Relay 3 Normally Open
Relay 1 Normally Closed
Relay 1 Common
Relay 1 Normally Open
Relay 3 Common
Relay 2 Normally Closed
Relay 2 Common
Relay 2 Normally Open
AI2 0–20 mA
AI2 0–10V
Default Setting
Description
10 Vdc Supply Source
0–10V
Voltage Speed Reference (Programmable to 4 mA to 20 mA)
Analog Input 1 Common (Ground)
4 mA to 20 mA
Current Speed Reference (Programmable to 0–10V)
Analog Input 2 Common (Ground)
I/O Ground for Reference and Control
Preset Speed B0
Sets frequency output to Preset Speed 1
Preset Speed B1
Sets frequency output to Preset Speed 2
Emergency Stop (T–)
Input forces VFD output to shut off
Force Remote (T+)
Input takes VFD from Local to Remote
Grounded
Allows source input
I/O Ground for Reference and Control
Control voltage output (100 mA max.)
Ready
Shows the drive is ready to run
Control voltage output (100 mA max.)
I/O Ground for Reference and Control
Output Frequency
Shows Output frequency to motor 0–60 Hz (4 mA to 20 mA)
Motor Current
Shows Motor current of motor 0–FLA (4 mA to 20 mA)
External control voltage input
Run Forward
Input starts drive in forward direction (start enable)
Run Reverse
Input starts drive in reverse direction (start enable)
External Fault
Input causes drive to fault
Fault Reset
Input resets active faults
Grounded
Allows source input
Fieldbus Communication (Modbus, BACnet)
Fieldbus Communication (Modbus, BACnet)
At Speed
Relay output 3 shows VFD is at Ref. Frequency
Run
Relay output 1 shows VFD is in a run state
At Speed
Relay output 3 shows VFD is at Ref. Frequency
Fault
Relay output 2 shows VFD is in a fault state
PowerXL DG1 Series VFD
AI2 10–10V