G e n e r a l i n f o r m a t i o n :
FS regulates the speed of fan motors according to
pressure changes. Make sure that the motor is approved
by the motor/unit manufacturer for variable speed by
means of phase cutting (TRIAC).
S a f e t y i n s t r u c t i o n s :
• Read operating instructions thoroughly. Failure
to comply can result in device failure, system
damage or personal injury.
• According to EN 13313 it is intended for use by
persons having the appropriate knowledge and
skill.
• Before opening any system make sure pressure in
system is brought to and remains at atmospheric
pressure.
• Do not exceed the specified maximum ratings for
pressure, temperature, voltage and current.
• Before installation or service disconnect all
voltages from system and device.
• Observe and avoid mechanical damage of
component housing.
• Do not use any other fluid media without prior
approval of EMERSON. Use of fluids not listed
could result in change of hazard category of
product and consequently change of conformity
assessment
requirement
accordance with European pressure equipment
directive 14/68/EU.
• Ensure that design, installation and operation are
according
to
European
standards/regulations.
• Disposal: Electrical and electronic waste must
NOT be disposed of with other commercial waste.
Instead, it is the user responsibility to pass it to a
designated collection point for the safe recycling
of Waste Electrical and Electronic Equipment
(WEEE directive 2012/19/EU). For further
information, contact your local environmental
recycling center.
S e t t i n g :
If desired set point differs from factory setting, follow
the procedure for setting before any installation:
Factory set point:
Type
Refrigerant Temp.
(°C)
R134a
36
R1234ze
46
FS_-41_
R513A
34
R450A
41
R404A
35
R507
35
R452A
37
R407F
38
FS_-42_
R448A
39
R449A
39
R407F
39
R407C
42
R22
42
FS_-43_ R410A
38
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
Pressure actuated Fan Speed Control
Fig. 1
Bottom view
Setting Screw
Sealing plug
1. Remove sealing plug and insert 2 mm or 5/64"
Allen key into setting screw. Turn Allen key
clockwise (+) or counterclockwise (-) to readjust the
setting. Do not turn setting screw more than 3
turns clockwise (+3).
Use following table as a quick guideline for setting:
Pressure changes per turn of adjusting screw:
Type
Pressure
range (bar)
Turn
clockwise
Turn
counter-
for
product
in
clockwise
2. After adjustment insert sealing plug and make sure
that it is properly fitted.
Notes:
and
national
• IP65 protection requires firmly sealed plug.
• Tolerances for condensing temperatures set point:
±2K.
Readjustment to factory set point:
Turn setting screw counterclockwise until end-stop.
Then turn setting screw clockwise:
5 turns for FS -41 ,
3 turns for FS -42 or
5-1/2 turns for FS -43 .
Partial voltage is applied even if motor is not
running. Disconnect voltage for service on motor or
FS!
M o u n t i n g l o c a t i o n : see Fig. 2 and Fig. 3
I n s t a l l a t i o n :
Pressure
P-band
Direct mounting via pressure connection or indirect
fix
mounting on housing bracket with capillary tube or
sweat pressure connection.
Threaded connection: (see Fig. 4)
8 bar
2.5 bar
• For tightness the use of copper gasket (
7/16"-20UNF female connection is required.
Brazing: (see Fig. 5)
• Perform and consider the brazing joint as per
EN 14324.
• Before and after brazing clean tubing and brazing
joints.
• Minimize vibrations in the piping lines by
15 bar
3.8 bar
appropriate solutions.
• Do not exceed the max. body temperature of
70°C!
E l e c t r i c a l c o n n e c t i o n f o r F S F - N _ _ :
Notes:
• Entire electrical connections have to comply with
21.8 bar 4.6 bar
local regulations.
• Use proper cable diameter for wiring of motor.
• Do not use with two-speed motors.
• Push plug slightly on the pins of controller.
• Direction of plug in 90° steps possible (Fig. 6)
• No gasket required.
• Fasten screw with 0,3 Nm.
• Plug cannot be repaired. In case of failure replace
connector.
www.climate.emerson.com/en-gb
Operating instruction
FSX / FSY / FSM
Allen Key
Clockwise
Counterclockwise
FS -41_
FS -42_
FS -43_
4.0...12.5 9.2...21.2 12.4...28.4
+1.2 bar
+2.5 bar
+3.3 bar
-1.2 bar
-2.5 bar
Date: 04.09.2019
P r e s s u r e T e s t :
After completion of installation, a pressure test must be
carried out as follows:
‒ according to EN 378 for systems which must comply
with
European
14/68/EU.
‒ to maximum working pressure of system for other
applications.
Warning:
• Failure to do so could result in loss of refrigerant
and personal injury.
• The pressure test must be conducted by skilled
persons with due respect regarding the danger
related to pressure.
L e a k a g e T e s t :
Conduct a tightness test according to EN 378-2 with
appropriate equipment and method to identify leakages
of external joints.
W i r i n g : ( s e e F i g . 7 )
Note: Use fuse type/size recommended by motor
manufacturer and break switch. Consult motor
manufacturer for capacitor size (Cb).
O p e r a t i o n :
Note: Before operation the customer has to qualify
the functionality and reliability of FS _+ FSF-N in
-3.3 bar
combination with the fan motors!
T e c h n i c a l D a t a :
Supply voltage
Nominal Current
FSY
FSX/FSM
Fig. 8
Max.operating Pressure PS
Max. Test Pressure PT
Fig. 4) on
Temperatures
medium at pressure connection
Medium
Compatibility
Protection class
Markings
(FS
+ FSF-N
)
FSY-FSX-FSM_OI_ML_R14_0716010.docx
pressure
equipment
directive
230VAC +15%, -20%
(50-60 Hz)
0.1 – 4.0A
0.5 – 4.0A
3.0A at 55°C - Fig. 8
FS -41 :
27 bar
FS -42 :
32 bar
FS -43 :
43 bar
FS -41 :
30 bar
FS -42 :
36 bar
FS -43 :
48 bar
Max. 70°C
operating (ambient)
-20...+55°C
R410A
R134a
R404a,
R507
R407C
R407A
R407F
R1234ze R452A
R448a
R449a
R450A
R513A
R22
IP 65 (EN 60529/IEC 529)
(EMC 2014/30/EU,
LVD 2014/35/EU,
RoHS 2011/65/EU)

Werbung

loading

Inhaltszusammenfassung für Emerson FSX serie

  • Seite 1 Turn +1.2 bar +2.5 bar +3.3 bar approval of EMERSON. Use of fluids not listed O p e r a t i o n : clockwise could result in change of hazard category of Note: Before operation the customer has to qualify...
  • Seite 2 Methode gemäß EN 378-2 so durchzuführen, dass Druckbereich mechanischen Beschädigungen entstehen. 4.0...12.5 9.2…21.2 12.4…28.4 Leckstellen sicher entdeckt werden. (bar) • Es dürfen nur von EMERSON freigegebene Medien eingesetzt werden. Die Verwendung nicht +1,2 bar +2,5 bar +3,3 bar Uhrzeigersinn V e r d r a h t u n g : ( s i e h e F i g . 7 )
  • Seite 3: Instructions De Service

    • Ne pas utiliser un autre fluide que ceux indiqués horaire taille et type recommandés par le fabricant du moteur. sans l’approbation obligatoire d’EMERSON. 2. Après le réglage, remettre en place le capuchon Consulter également le fabricant pour la taille du L'utilisation d'un fluide non approuvé...
  • Seite 4 -1.2 bar -2.5 bar -3.3 bar previamente aprobado por EMERSON. El uso de Nota: Usar el tamaño de fusible recomendado por el 2. Después del ajuste coloque el tapón y asegúrese de fabricante del motor y el interruptor de corte.
  • Seite 5: Istruzioni Operative

    • quattro posizioni a 90° possibili (Fig. 6) RoHS 2011/65/EU) • Non è richiesta guarnizione. • Serrare la vite con una coppia di 0.3 Nm. Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Am Borsigturm 31 I 13507 Berlin I Germany Date: 04.09.2019...
  • Seite 6 (FS + FSF-N LVD 2014/35/EU, регулятор с двухскоростными RoHS 2011/65/EU) эл.двигателями. FS_-43_ R410A 21.8 бар 4.6 бар • Осторожно одеть разъем на выводы регулятора. Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Am Borsigturm 31 I 13507 Berlin I Germany Date: 04.09.2019 FSY-FSX-FSM_OI_ML_R14_0716010.docx...
  • Seite 7 Blue/ blau/ bleu/ azul/ blue/ Синий  Brown/ braun/ marron/ marrón/  marrone/ Коричневый Fuse 4A/ Sicherung 4A/ fusible 4A/  fusible 4/ fusibile 4/ Предохранитель 4А Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Am Borsigturm 31 I 13507 Berlin I Germany Date: 04.09.2019 FSY-FSX-FSM_OI_ML_R14_0716010.docx...

Diese Anleitung auch für:

Fsy serieFsm serieFsx 41Fsx 42Fsx 43Fsy 41 ... Alle anzeigen