Herunterladen Diese Seite drucken

Risk Of Electric Shock - Bosch FLM-420-RHV-S Produktbeschreibung / Montageanleitung

Vorschau ausblenden Andere Handbücher für FLM-420-RHV-S:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 13
English
Functional Description
The interfaces have two change−over contact relays (Form C) for the controlled activation of external ele-
ments (e.g. ·smoke flaps, extinguishing systems, or fans) at LSN fire panels.
It is not permitted
to operate the relay with different voltages (high voltage and low voltage)
to place two different AC line voltage phases on the relay contacts
INFO
to use

RISK OF ELECTRIC SHOCK !

Danger of life with contact of live parts and wires.
" Disconnect power before connecting equipment!
DANGER
" Before connecting the power supply make sure that the contact protection is fixed and
locked in place (see page 5 resp. 7).
Wiring
Description
NC / COM / NO
NC / COM / NO
b1+ / a− / b2+
FB2 +
FB1/FB2 −
FB1 +
Address Setting
Technical Specification
Operating/display elements
Function selection
Address setting 0 0 0
Address setting 1...254
Address setting CL 0 0
Input voltage (min − max)
Maximum current consumption
Max. relay contact rating
Fuses
Feedback current
Feedback voltage
Safety class as per IEC 60950
Protection class as per IEC 60529
Permitted operating/storage temperature
Permitted relative humidity
Material interface module housing
Material surface−mount housing
Product Description FLM−420−RHV−S / FLM−420−RHV−D
different adressing modes together.
Connection
Relay 1
Relay 2
Relay 2, Feedback +
Relay 1 und 2, Feedback −
Relais 1, Feedback +
Mode/
X
X
XX
X
FAN
RLHV
LSN
X
X
XX
2 LEDs (1x red, 1x green)
FAN or RLHV function via rotary switch
Loop/stub in LSNi mode with automatic addressing
(T−tap system not possible)
Loop/stub/T−tap system in LSNi mode with manual
addressing
Loop/stub in „classicˆ LSN mode
15 V DC − 33 V DC
15,5 mA
10 A bei 120 V AC / 230 V AC / 24 V DC,
6 A bei 30 V DC
F1 = 10 A, F2 = 10 A
max. 1 mA (EOL resistance R=3.9 kW)
max. 30 V DC
II
FLM−420−RHV−S: IP 54 / FLM−420−RHV−D: IP 30
−20 _C . . . 50 _C / −25 _C . . . 85 _C
< 96%
PPO (Noryl)
ABS + PC−Blend
19 / 36
FPA−
BZ 500 LSN
5000
UEZ 2000 LSN
UGM 2020
n
CL 0 0
n
0 0 0
n
1...254
_
255...299
610−F.01U.003.282 / A2
ST −FIR / PRM1 / zab
n
_
_
_

Werbung

loading

Diese Anleitung auch für:

Flm-420-rhv-d