3 Mechanical installation

DANGER
The Solar Inverter must not be installed in areas
subject to explosion hazards.
The Solar Inverter must not be exposed to caustic
gases.
No combustible materials must be stored within 3
metres of the Solar Inverter.
Observe the following minimum distances:
Ceiling
warm
300 mm
air
cold
300 mm
air
The installation surface must consist of flame-retard-
ant material.
The Solar Inverter must be installed vertically.
Solar Inverters must not be stacked.
The ambient temperature must be between -25 °C
and +40 °C (AT) / -25 °C and +45 °C (NT).
The Solar Inverter should not be exposed to direct
solar radiation.
Due to its high IP 54 rating the device is suitable for
installation indoors and in covered external areas.
Installation
1 Install the wall bracket. 10 mm dia. bore hole.
2 Attach the Solar Inverter. Release the locking
screw and slide the Solar Inverter into the two
slots at the top of the mounting frame.
3 Secure the Solar Inverter by tightening the lock-
ing screw.