Installation
driver to open and close the terminal for attaching the two power supply
wires of a 24 V DC power supply. Connect the wires according to the pin
assignment on the label.
Turn the power on when all cables are connected to the SYMPL dali Node.
The device starts booting. The device has finished booting and is in
operation when the LED Status is flashing.
The dali Node runs a power supply check automatically but only at the first
instant after switching on. The power supply check scans the DALI bus
system for alien power supply and incorrect voltage. In case of alien power
supply or incorrect voltage, the DALI bus will not be powered.
For electrical safety reasons it is not allowed that SYMPL dali
!
Nodes share the same power supply with other SYMPL
nodes, such as SYMPL dmx Node etc.
Please make sure to use one dedicated power supply unit
only for the DALI devices.
The SYMPL dali Node is not suited for powering over a DC
!
power supply network. Use a separate certified SELV Class 2
power supply unit in the control cabinet for supplying 24 V
DC to the SYMPL dali Node.
Detach from the power supply whenever working on the
i
DALI bus or any attached DALI devices. DALI bus related
changes can cause damage to the installation and are only
detected after switching on the SYMPL dali Node. A power
supply check for the DALI bus system executes.
A Mean Well DR-15-24 power supply unit is recommended.