PoE:
For PoE, simply connect an Ethernet connection from a power sourcing
device.
External power supply:
Connect the SYMPL serial Node to a certified NEC Class 2 24 V DC power
supply unit. Present power supply equates to the status "On" or running of
the SYMPL Node.
To connect the device to a power supply unit, use the provided 2-pole
terminal and lay the wires as stated on the front label. The voltage
assignment is left V+ and right V-.
Turn the power on when all cables are connected to the
SYMPL serial Node. The device starts booting. The device has finished
booting and is in operation when the LED Status is flashing.
The SYMPL serial Node is not suited for powering over a DC
!
power supply network. Use a separate certified SELV Class 2
power supply unit in the control cabinet for supplying 24 V
DC to the SYMPL serial Node.
5

Network configuration

The configuration of the e:cue SYMPL serial Node is done via e:cue
SYMPHOLIGHT. See the SYMPHOLIGHT System Manual for details on
configuration, available at www.ecue.com.
The network properties of the SYMPL serial Node are preconfigured. The
successful installation of the power supply is required for changing the
network configuration. You can either adjust the network settings with
SYMPHOLIGHT or using the web interface of the SYMPL serial Node.
Network configuration
15