The installation of the SYMPL serial Node consists of mounting the device,
connections to e:net, to power supply, and of devices to the serial ports.
The sequence of cabling is not defined. Supply the SYMPL serial Node with
power after all cabling is completed; it starts booting.
Connect cables and data only when the device is powered
!
down.
Each cable should not exceed a length of 30 m.
!
4.1
Installation conditions
Installation position:
Horizontal spacing:
Minimum vertical rail grid spacing:
Recommended vertical rail grid spacing:
Installation location
4.2
Mounting process
The e:cue SYMPL Node is designed to mount onto a 35 mm DIN rail
(EN 60715) in a vertical position.
Terminals on top and bottom
No spacing necessary
115 mm (90 + 25 mm)
(excluding conduit)
160 mm (with 40 mm conduit)
Indoor
1. Clip the device to the rail from
top.
2. Gentle pressure is then
applied to the top front to snap it
in place. The SYMPL serial Node
has been mounted successfully.
Installation