Herunterladen Inhalt Inhalt Diese Seite drucken

Instructions For Operation And Use; Basic Information; Frequency Converter Operation - Elektror A-HP series Betriebs- Und Montageanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Operating and assembly instructions A-HP
4 INSTRUCTIONS FOR OPERATION
AND USE
EN

4.1 Basic information

Please observe the notes on designated use in section 1.1,
as well as the safety guidelines in sections 1.2 to 1.14.
If electrical current drops below the rated current of the drive
motor during operation, check to see if the mains voltage and
frequency match the appliance ratings.
After protective shutdowns, e.g. tripping of the motor circuit-
breaker, activation of the PTC evaluation unit by motors with
a PTC resistor sensor, or after a protective shutdown of the
frequency converter during FU applications, the appliance
must not be restarted until the problem has been trouble-
shooted.
If the blower cannot be operated over the whole range of the
characteristic curve, the motor may overload if the system
resistance is too low (excessive current consumption). The
volumetric air fl ow should be reduced in this case by means
of a throttle valve fi tted on the intake or discharge side.
The blower must not be subjected to vibration or impact
loads.

4.2 Frequency converter operation

A frequency converter is used, allowing a wide range of
speed adjustments. There is only a small, load-related dif-
ference in rpm between idle state and the max. load of the
blowers and the lateral channel blower.
To ensure trouble-free operation of blowers and side
channel blowers, it is important that the converter meet
the following requirements:
• Converter output equal to or greater than motor power
output *)
• Converter current equal to or greater than motor current *)
• Converter output voltage equal to rated motor voltage
• Supply voltage max. 480V, including 5% voltage tolerance
• The pulse frequency of the converter should be 8 kHz,
because a lower pulse frequency will lead to noisy motor
operation
• The values for the maximum/minimum frequency can be
found at 1.10.
14
• The converter should have a connection for a tempera-
ture sensor (PTC resistor sensor) or a temperature switch
(normally-closed contact)
*) Refer to the rating plate for data
The motor can be operated in a delta or star-point confi gura-
tion, depending on the input voltage of the converter.
The following U/f assignments must be confi gured at the
converter.
U
B
0
f
and U
B
B
If this is ignored, the motor current will increase dispropor-
tionately and the drive motor will fail to achieve its rated
speed.
Prohibited
range
f
B
= refer to rating plate
Warning!
To avoid personal damage, destruction of the
blower or motor overload, a higher frequency
(speed) than the frequency (f
rating plate must never be set on the converter
otherwise the motor may be overloaded or the
blower destroyed due to the increased speed. The
temperature sensors are connected to the corre-
sponding converter inputs to protective the drive
motor. Single-phase alternating current motors
are not suitable for converter operation.
It is absolutely essential that you observe the
installation and safety instructions described in
the respective operating or application manuals
provided by the frequency converter supplier to
guarantee a safe and trouble-free operation.
It is also important to note that special ambient
conditions may lead to a high level of contamina-
tion of the cooling fi ns with the FUK devices. The
frequency converter switches off if the cool-
ing output on the cooling fi ns is not adequate.
Regular cleaning is required for devices in these
environments.
Note!
The following times apply for the respective
device motor output class (see rating plate) with
run-up/expiry as well as speed changes in order
to avoid high component loads and faults in the
converter operation:
Device motor output
0,25 kW < Motor output <=
3,0 kW
3,1 kW < Motor output
<= 7,5 kW
7,6 kW < Motor output
<= 11,0 kW
11,1 kW < Motor output
<= 30 kW
A uniform run-up and expiry must be guaranteed within the
run-up and expiry times.
No speed changes must occur during operation that exceed
the speed change during run-up and expiry.
Please note also that, in certain ambient conditions, heavy
soiling of the cooling fi ns can occur in FUK-compliant ap-
pliances. If the cooling capacity of the cooling fi ns is insuf-
fi cient, the frequency converter will shut down. Appliances
which are operated in these environments must be inspected
on a regular basis.
Protection by residual-current-operated circuit breaker
(FI circuit-breaker):
The present IGBT frequency converters produce discharge
currents of >=3.5 mA due to their design principle. These dis-
charge currents can lead to unwanted tripping in systems
protected by a 30 mA-FI circuit-breaker.
If a fault occurs, fault currents can also discharge through the
PE conductor as direct current. If protection is needed on the
supply side by means of an FI circuit-breaker, then an ACDC
sensitive (type B) FI circuit-breaker must be used. Use of an
FI circuit-breaker other than type B can cause death or seri-
ous injury if a fault occurs.
To meet the EN 61800-5-1 standard, the PE conductor must
be duplexed and routed through separate terminals or have
a cross-section of at least 10 mm² Cu.
www.elektror.com
) specifi ed on the
B
Run-up time
Expiry time
[s]
[s]
10
20
20
40
30
60
30
60

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis