Herunterladen Diese Seite drucken

Installation; General; Condensate Pipe - Dimplex LA 22TBS Montage- Und Gebrauchsanweisung

Luft-wasser-wärmepumpe für aussenaufstellung
Vorschau ausblenden Andere Handbücher für LA 22TBS:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

English
5

Installation

5.1 General

The device should always be installed on a permanently
smooth, even and horizontal surface. The entire frame should
be in direct contact with the ground in order to ensure an ade-
quate soundproof seal, to prevent the water-bearing compo-
nents from becoming too cold and to protect the inside of the
device from small animals. If this is not the case, additional insu-
lation measures may be necessary. To prevent small animals
from entering the inside of the device, the connection hole in
the base plate must be sealed, for example. Furthermore, the
heat pump should be set up so that the air outlet direction of
the fan is perpendicular to the main wind direction to allow un-
restricted defrosting of the evaporator. The heat pump is de-
signed for installation on even ground. In the case of different
conditions (e.g.: installation on a platform or flat roof) or there is
a greater risk of the heat pump tipping over (due to an exposed
position or high wind exposure), additional protection against
tipping over must be provided. The responsibility for the heat
pump installation lies with the specialist system construction
company. During the installation, local requirements such as
building regulations, static load of the building, and wind expo-
sure must be accounted for.
It must be possible to carry out maintenance work without hin-
drance. This is ensured when observing the distances to solid
walls as shown in the figure.
0,5 m
0,5 m
0,5m
ATTENTION!
Do not restrict or block the area around the air intake or outlet.
ATTENTION!
Observe country-specific building regulations!
ATTENTION!
The physical impacts must be observed for installation close
to walls. No windows or doors should be present in the area
surrounding the air outlet of the fan.
ATTENTION!
In cases of installation close to a wall, there may be more
sediment in the air inlet and outlet areas due to the air current.
The colder outside air outlet should discharge in such a way as
to not increase the heat losses in heated neighbouring rooms.
EN-6
ATTENTION!
Installation in a hollow or in an inner courtyard is not
permitted because cooled air collects at ground level and is
drawn in again by the heat pump during extended periods of
operation.

5.2 Condensate pipe

Condensate that forms during operation must be drained off
frost free. To ensure proper drainage, the heat pump must be
mounted horizontally. The condensate pipe must have a mini-
mum diameter of 50 mm and must be fed into a sewer in such
a way that it is safe from frost. Do not discharge the condensate
directly into clearing tanks or cess pits. The aggressive vapours
and a condensate pipe laid in an area which is not frost-free can
destroy the evaporator.
ATTENTION!
The frost line can vary according to the climatic region. The
regulations of the countries in question must be observed.
2 m
452166.66.01 · FD 9912
LA 22TBS - LA 28TBS
www.gdts.one

Quicklinks ausblenden:

Werbung

loading

Diese Anleitung auch für:

La 28tbs