Application 1: Basic Speed Control (default)
This Application is ideal for general purpose applications. It provides push-button or switched start/stop control. The
setpoint is the sum of the two analogue inputs AIN1 and AIN2, providing Speed Setpoint + Speed Trim capability.
SINGLE
WIRE
STARTING
10k Speed
A or V
Setpoint
default source
= 4-20mA
User Relay
Control
Terminal
10
DIN4/DOUT2
NOT STOP
9
DIN3
JOG
8
DIN2
DIRECTION
7
DIN1
RUN FORWARD
6
+24V
24V
5
AOUT
RAMP OUTPUT
4
+10V REF
+10V REF
3
AIN2
SPEED TRIM
2
AIN1
SPEED SETPOINT
1
0V
0V
RL1A
DOUT3
RELAY SOURCE
RL1B
Applications
24V = RUN FWD & RUN REV signals latched,
0V = RUN FWD & RUN REV signals not latched
24V = jog
0V = remote forward, 24V = remote reverse
24V = run forward
= 1
DEMAND (0V = 0%, 10V = 100%)
= 3
4mA = 0%, 20mA = 100%
= 0
0V = 0%, 10V = 100%
= 1
HEALTH i.e. 0V = not healthy