General information:
FX5 - FX9 are stepper motor driven valves for precise
control of refrigerant mass flow in air conditioning,
heat pumps, industrial cooling process and close
control systems as: Expansion valves and Liquid
injection valves.
!
Safety instructions:
• Read operating instructions thoroughly. Failure
to comply can result in device failure, system
damage or personal injury.
• In a severely contaminated system, avoid
breathing acid vapors and avoid contact with skin
from contaminated refrigerant / lubricants.
Failure to do so could result in injury.
• Before opening any system make sure pressure in
system is brought to and remains at atmospheric
pressure.
• Do not exceed the specified maximum ratings for
pressure, temperature, voltage and current.
• Do
not
release
any
refrigerant
atmosphere!
• Before installation or service disconnect all
voltages from system and device.
• Do not operate the valve when the compressor is
not running.
• Do not use any other fluid media without prior
approval of EMERSON. Use of fluids not listed
could result in change of hazard category of
product and consequently change of conformity
assessment
requirement
accordance with European pressure equipment
directive 97/23/EC.
Mounting location/ Mounting direction:
• The valve has to be installed in horizontal position to
vertical position. Motor must not be directed
upwards as in Fig. 1.
• Valves
are
delivered
with
connection configuration and an external tightness of
-6
6.4*10
mbarl/s. If the system piping requires,
flange can be positioned in 4 directions (see Fig. 2).
Use the spare O-ring in packaging if needed and
tighten screws with Allen key acc. table below.
Technical Data:
Type
Maximum working pressure PS:
Medium inlet temperature TS:
Connection, DN & Dimensions
Fluid group
Refrigerant: R22, R134a, R407C, R410A
Hazard category: PED 97/23/EC
Nominal Supply Voltage U:
Maximum Current Imax.:
Marking
Emerson Climate Technologies GmbH
Holzhauser Str. 180 | 13509 Berlin | Germany
Electronic Expansion Valves
FX5 / FX6 / FX6.5 / FX7 / FX7.5 / FX 8 / FX9
Valve
FX5/6/6.5
FX7
FX7.5/8
FX9
• For best result, locate the valve as close as possible
to the distributor or inlet of evaporator.
• Flow directions: operating conditions (see Fig. 3)
Valve
FX5
FX6
FX6.5
FX7
Brazing: (Fig. 4)
into
the
• Use the wet rags during brazing when the valve
flange is already mounted.
• To avoid oxidization, it is advised to purge the
system with an inert gas such as nitrogen while
brazing.
• Never braze the valve when the valve is fully in
close position.
Installation:
• Protect the valve against vibration. If the total valve
for
product
in
weight results in excessive stress to the piping joints,
the valve must be supported by suitable mounting
bracket(s).
• The valves are delivered in half open position for
vacuuming after brazing. Before charging the system
with refrigerant, close the valve in order to prevent
migration of refrigerant to evaporator.
straight
through
• Check for sufficient refrigerant charge/subcooling
and make sure no flash gas is present at the inlet of
valve before attempting to check valve operation.
Install an EMERSON sight glass AMI or MIA before
the valve.
• The valve must be protected against contaminants.
Install an EMERSON filter drier before the valve.
FX5
24 VDC
0.8 A
& UL
(pending)
www.emersonclimate.eu
Operating Instructions
Wrench
size
for flange
Screw Size
[mm]
tightness [Nm]
M5x12-8.8
4
M5x16-8.8
5
M5x25-8.8
8
M5x25-8.8
8
MOPD [bar]
Normal flow
Reverse flow
direction
direction
A→B
B→A
40
30
35
30
35
30
35
35
FX6
FX6.5
-
-
-
24 VDC
24 VDC
0.8 A
0.8 A
& UL
& UL
(pending)
(pending)
Date: 12.02.2015
Note:
Torque
The interior parts of valve must be protected
against moisture and water at any time. It is not
permitted the use of water, steam or any other
2.5
solvent to the inside of valve for cleaning purpose
4.3
Pressure test:
21
After completion of installation, a pressure test must be
21
carried out as follows:
- according to EN 378 for systems which must comply
with
European
97/23/EC.
Warning:
• Failure to do so could result in loss of refrigerant
and personal injury.
• The pressure test must be conducted by skilled
persons with due respect regarding the danger
related to pressure.
Tightness test:
Conduct a tightness test according to EN 378-2 with
appropriate equipment and method to identify leakages
of external joints. The allowable leakage rate must be
according system manufacturer's specification.
Electrical Connection:
• Entire electrical connections have to comply with
local regulations.
Warning:
• Improper wiring will result wrong direction of
rotation or no rotation of stepper motor.
Wiring and mounting of plug: (Fig. 5).
• Prewired plug and cable assembly (EXV-Mxx) is
ready for connection to the valve. There is no
specific requirement for positioning of plug on pins
1. Push the plug on pins on top of the valve.
2. Rotate the nut one turn in clockwise direction and
push the plug.
3. Repeat this procedure until the plug is tightened.
Wiring to driver/controller:
• See wiring diagram of used driver/controller.
Service / Maintenance:
• For motor check, use an ohmmeter with suitable
range and connect it as shown in Fig. 6.
FX7
FX7.5
46 bar
-35°...70°C
see Fig. 7
II
I
I
24 VDC
24 VDC
0.8 A
0.8 A
& UL
& UL
(pending)
(pending)
pressure
equipment
directive
FX8
FX9
35 bar
I
I
24 VDC
24 VDC
0.8 A
0.8 A
& UL
& UL
(pending)
(pending)

Werbung

loading

Inhaltszusammenfassung für Emerson FX5

  • Seite 1 Operating Instructions Electronic Expansion Valves FX5 / FX6 / FX6.5 / FX7 / FX7.5 / FX 8 / FX9 Note: General information: Wrench Torque The interior parts of valve must be protected FX5 - FX9 are stepper motor driven valves for precise...
  • Seite 2: Elektronische Expansionsventile

    Betriebsanleitung Elektronische Expansionsventile FX5 / FX6 / FX6,5 / FX7 / FX7,5 / FX 8 / FX9 Beschreibung: Drucktest: Schlüssel- Drehmoment Nach der Installation ist ein Drucktest durchzuführen: FX5 - FX9 sind schrittmotorgesteuerte elektronische für dichten Schrauben- weite - gemäß EN 378 für Geräte, die die Europäische für...
  • Seite 3: Informations Générales

    Instructions de service Détendeur Electronique FX5 / FX6 / FX6,5 / FX7 / FX7,5 / FX 8 / FX9 Note: Informations générales: • La partie intérieure de la vanne doit être protégée Taille Couple de Les détendeurs FX5 - FX9 sont des vannes actionnées de la clé...
  • Seite 4: Instalación

    Instrucciones de funcionamiento Válvulas de expansion electrónicas FX5 / FX6 / FX6,5 / FX7 / FX7,5 / FX 8 / FX9 Nota: Información general: Las partes interiores de la válvula deben ser Tamaño llave Par de apriete FX5 - FX9 son válvulas de motor paso a paso para el protegidas de la humedad en todo momento.
  • Seite 5 Instruzioni operative Valvole di Espansione Elettroniche FX5 / FX6 / FX6,5 / FX7 / FX7,5 / FX 8 / FX9 Nota: Informazioni generali: Coppia Le parti interne della valvola devono essere Le valvole FX5 - FX9 sono azionate da un motore protette dall’umidità...
  • Seite 6: Общая Информация

    Руководство по эксплуатации Электронные расширительные клапаны FX5 / FX6 / FX6,5 / FX7 / FX7,5 / FX 8 / FX9 Общая информация: Испытание на прочность: Ключ Момент Клапаны с шаговым двигателем После окончания монтажа испытание на FX5 - FX9 Клапан...
  • Seite 7 Electronic Expansion Valves FX5 / FX6 / FX6.5 / FX7 / FX7.5 / FX 8 / FX9 Fig. /рис. 1 Fig. /рис. 3: Fig. 5 Fig. / рис. 2 Fig. / рис. 4 Fig./ рис. 6 3,4 Ω 3,4 Ω...

Diese Anleitung auch für:

Fx6Fx6.5Fx7Fx7.5Fx 8Fx9