Herunterladen Inhalt Inhalt Diese Seite drucken

Maintenance; Troubleshooting - Galletti FC/NT Serie Iinstallation, Gebrauch Und Wartung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 8
8

MAINTENANCE

For safety reasons before carrying out any maintenance or cleaning opera-
tion, switch off the unit turning the selection switch to "Stop" and the power
supply switch on position 0 (OFF).
Be careful during any maintenance operation; you could get injured by some
metal parts; use protective gloves.
The fan coils FC/NT do no require any particular maintenance operation: only the
periodical cleaning of the air filter should be carried out.
It is necessary to carry out a running in period of 100 hours in order to eliminate
all mechanical friction.
The starting up must be carried out at the maximum speed.
For good operation of the fan coils FC/NT follow the instructions below:
- keep the air filter clean;
- do not pour liquids into the unit;
- do not introduce metal parts through the air outlet grill.
- keep the air inlet and outlet free at all times.
Each time the machine is turned on after being idle for a long period, ensure there
is no air in the heat exchanger.
Before using the unit for air conditioning, check that:
- condensate drainage is performed correctly:
- the heat-exchanger fins are not obstructed by deposits of dirt.
If necessary clean the fins with low pressure compressed air or steam without
damaging them.
9
CLEANING
For safety reasons before carrying out any maintenance or cleaning opera-
tion switch off the unit turning the selection switch to "Stop" and the power
supply switch on position 0 (OFF).
Clean the filter at least once a month and in any case before using the unit
(before the heating or the air conditioning season).
For cleaning the air filter proceed as follows:
- take out the air filter as shown in figure 7 page 20;
- clean the filter with lukewarm water , or in case of dry dust, with compressed air;
- reassemble the filter after having dried it up.
It is recommended to replace the air filter yearly, and to use original spare parts;
the fan coil model is reporter on the nameplate located on the internal part of the
right side where electric wiring is present
The filter sizes are reported in figure 2 page 18.
To clean the unit cabinet proceed as follows:
- use a soft cloth;
- do not pour any liquid on the unit, as this could cause electrical shocks or
damage the components inside it;
- do not use any aggressive chemical solvents; do not use very hot water to clean
the air outlet grill.
10

TROUBLESHOOTING

If the unit does not work properly first check the points reported in the table below
before requesting service. If the problem cannot be solved contact your dealer
or service centre.
Problems
Cause
The unit does not run at all
1 Power failure
2 Leakage breaker tripped
3 The switch is on STOP
position
Poor cooling or heating per-
1 Dirty or clogged air filter
formance
2 Obstacle near the air inlet or
outlet
3 Air
inside
exchanger
4 Doors and windows are open
5 The unit is running at low
speed
The unit leaks
1 The unit is not levelled
2 Drip tray is clogged
Solution
1 Restore power
2 Contact service centre
3 Turn on the unit selecting "I"
1 Clean air filter
2 Remove the obstacle
the
heat
3 Contact the installer
4 Close doors and windows
5 Select medium or high fan
speed
1 Contact the installer
2 Contact the installer
5
GB
1800202 - rev. 01

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Inhaltsverzeichnis