Device LEDs
green-red LED "DEVICE":
yellow-green LED "OUT":
red LED "SF":
LED flashing codes of the red LED "SF" in priority sequence

Technical data

Input data (L1 - L2 - L3)
Measuring/motor voltage
Input resistances
Response threshold U
an
Standstill time t
s
Aux. voltage U
(A1 - A2)
H
Recommended fusing
Voltage range
AC
DC
Rated consumption
Rated frequency
PFH
SFF
T1
4
lights up green during operation
lights up red in the event of internal device
faults
lights up yellow when EMF > U
an
lights up green upon expiry of t
s
green continuous light upon enabling of the
output contacts
lights up upon faults in the measuring and
feedback circuit and when the auxiliary volt-
age U
is too low (see flashing code)
H
max. 690 V AC
approx. 400 k
approx. 20 mV ... 400 mV, settable
0.2 ... 6 s settable
230 V AC, 400 V AC and 24 V DC
2 A
0.8 ... 1.1 U
N
0.9 ... 1.2 U
N
approx.. 5 VA, 3 W
50 / 60 Hz
-9
1.49 x 10
1/h
95.5 %
175,200 h
Output data
Number of contacts
Contact type
Rated output voltage
Thermal current I
th
2
Total I
Square-law summation current
Max. permissible current up to 40°C
over 3 rows of contacts = 5 A
Max. permissible current at 60°C over
3 rows of contacts = 2 A
Switching capacity
to 15 AC
NO
NC
to 13 DC
Recommended fusing of the safety
contacts
Maximum number of switching opera-
tions
Contact service life
at 230 V AC/ 5 A cos ϕ 0,5
Mechanical service life
Semiconductor signaling outputs
Changeover signaling contacts
General data
Rated operating mode
Temperature range
Operation
Storage
Creepages and clearances
Rated impulse voltage / degree of con-
tamination
Terminals L1 / L2 / L3 between each
other
Contacts 11/12, 23/24, 33/34, 43/44 to
the rest
Contacts 11/12, 23/24, 33/34, 43/44 to
each other
Signaling contacts to the rest
Semiconductor outputs A3 / 64 / 74 /
A4 to the rest
Aux. voltage A1 / A2 to the rest
at AC auxiliary voltage
at DC auxiliary voltage
Control terminals X1 / X2 / X3
Degree of protection
Enclosure
Terminals
Vibration strength
Quick mounting
Net weight
3 NO, 1 NC
Relay, positively driven
250 V AC
5 A (up to 40°C)
see derating curve (Fig. III)
2
2
2
= I
+ I
+ I
1
2
3
I
, I
, I
- current in the contact paths
1
2
3
2
2
2
2
5
+ 5
+ 5
= 75 A
2
2
2
2
2
+ 2
+ 2
= 12 A
3 A / 230 V AC
IEC/EN 60 947-5-1
2 A / 230 V AC
IEC/EN 60 947-5-1
2 A / 24 V DC
IEC/EN 60 947-5-1
5 A quick-response
1200 / h
5
2 x 10
operating cycles
6
50 x 10
operating cycles
100 mA 24 V DC, plus-switching, electri-
cally iisolated; supply via A3 / A4; "64" for
enabling, "74" for faults
3 A 250 V AC (in working position for ena-
bling) (51/54)
Continuous duty
- 25 ... + 60°C
- 40 ... + 75°C
IEC 60 664-1
6 kV / 2
6 kV / 2
4 kV / 2
4 kV / 2
4 kV / 2
6 kV / 2
4 kV / 2
no electrical isolation to L1 / L2 / L3
IP 40
IEC/EN 60 529
IP 20
IEC/EN 60 529
Amplitude 0.35 mm
Frequency 10 ...
IEC/EN 60 068-2-6
55 Hz
Standard mounting
IEC/EN 60 715
rail
approx. 500 g
Order No.: 3ZX1012-0TK28-7BA1