PROGRAMMING THE OPERATIONAL LOGIC
It is possible for the control unit to use several different operational logic states, by simply moving the dip-switches located on the card.
The functions associated with each individual dip-switch are listed below.
DIP
FUNCTION
DEAD MAN
1
function
2
CLOCK Function
3
Start Command
Automatic
4
Closure
Start when
5
Opening
Inversion mode
6
(START1)
7
Pre-flashing
8
Photocell
9
Test Photocell
Type of Safety
10
Device
11
Safety Device
Test Safety
12
Device
FAULT MESSAGES
At the start of each operating cycle, the controller performs
an operational test of the motor drive circuit (Triac).
Furthermore, if enabled by the relative dipswitch, it also
performs a test of the photocell and safety device inputs.
If a fault occurs, the cycle does not start.
SETTING
DESCRIPTION
ON
Enabled
The user opens and closes maintaining this command active
OFF
Disabled
ON
Enabled
When the START2 input is activated, the shutter opens and automatically closes
only after the input is deactivated
OFF
Disabled
ON
Up-Down
START1 controls opening / START2 controls closure
OFF
Start-Stop
START1 controls opening and closure / START2 is disabled
ON
Enabled
The rolling shutter is closed automatically after the time set on the PAUSE trimmer
The rolling shutter remains open when the open phase ends. Closure must be
OFF
Disabled
commanded with another START command
ON
Enabled
A START command during opening is ignored
OFF
Disabled
A START command during opening is accepted
ON
Enabled
START during opening causes closure. START during closure causes opening.
OFF
Disabled
Step-Step Operation
ON
Disabled
The blinker turns on when the motor is activated
OFF
Enabled
The blinker turns on for 2 seconds and then the motor is started
Activation of the photocell during opening or closing causes the shutter to stop.
ON
Always active
When the photocell is reset, the shutter will open completely.
NOT active during
Activation of the photocell during opening is ignored. Activation of the
OFF
opening
photocell during closing causes the complete reopening of the shutter.
The controller performs a functional test on the photocells before starting each
ON
Enabled
open or close operation. If the photocells doe not function correctly, the shutter
will not move and the blinker will blink for about 8 seconds.
OFF
Disabled
WARNING: Correctly connect the TX of the photocell (see page 10).
Conductive rubber
Select this operation if you use conductive rubber safety devices with a nominal
ON
edge
resistance of 8K2.
Standard or optical
Select this option if you use traditional safety devices with a normally closed
OFF
edge
(NC) contact or with an optical safety device.
Activation of the safety device during opening or closing causes the shutter to
ON
Always active
stop. Automatic closure is cancelled
Activation of the safety device during opening is ignored. Activation of the
NOT active during
OFF
safety device during closing causes the complete reopening of the shutter.
opening
Automatic closure is cancelled
The controller performs a functional test of the safety devices before each open
ON
Enabled
or close start. If the safety devices do not function correctly, the shutter will not
move and the blinker will blink for about 8 seconds.
Do NOT enable the test function if you use conductive rubber safety
devices or traditional safety devices that are not equipped with a
OFF
Disabled
special controller for their operation.
The messages are indicated by the warning light:
• Blinks about 4 seconds: Triac fault (or motor disconnected)
• Blinks about 8 seconds: Photocell or safety device fault
12