Connecting External Equipment

„ External Input Wiring
z Type of wiring
Use a flexible wiring of 0.5 to 0.75 mm
z Total Wire Length
100 m or less
If a longer length is needed,use a relay.
„ Connection Specifications
Condition
Non-voltage contact "a"
Static or Pulse
• Contact allowable
Control
voltage:
input
DC5 V ± 10%
• Contact allowable
current:
Max. 10 mA
„ External Output Wiring
z Exteranl output wiring specification is the same as external input wiring .
z When outputting the operation status or alarm status, a 12 V DC external power
source for relays is required.
• Recommended product: COSEL PBA10F-12
• Allowable wattage: 15 W or less
z Use the following specifications for DC power wiring.
• Type of wiring: Use a flexible wiring of 0.5 to 0.75 mm
• Arrange the power line as short as possible.
„ Connection Specifications
Condition
Non-voltage contact
"a" Static or Pulse
DC Power
There is a polarity.
input
(Make sure that the
polarity (+/-) is correct
before connecting.)
Voltage contact "a"
Static (Relay output)
• Contact allowable
voltage:Max. DC12 V
Status
output
• Contact allowable
current:Max. 100 mA
• Minimum application
load:DC5 V 1 mA
• Use only a single wiring or stranded wiring.
.
2
• Wiring tip arrangement.
• Arrange the external output wiring as well.
Controller side
Terminal name
Input 1 (IN 1)
Input 2 (IN 2)
Common (COM)
Controller side
Terminal name
DC power +
(DC 12 V +)
DC power -
(DC 12 V -)
Alarm output
(OUT 1)
Operation Output
(OUT 2)
Common (COM)
Attention
Wiring
External equipment side
Terminal
Circuit example
1
2
3
COM
2
External equipment side
Terminal
Circuit example
4
+
DC power
(12 V)
5
-
Coil
6
Relay
7
Relay
8
9 mm~10 mm
Condition
• Pulse width:
300 msec or
more
Condition
• Power Supply
for relays
(Supply 12 V DC
externally)
• Rated coil voltage:
12 V DC
25