Herunterladen Inhalt Inhalt Diese Seite drucken

Checking Connections - Beninca Core Handbuch

Vorschau ausblenden Andere Handbücher für Core:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 16
1) CONTROL PANEL CORE
1.1) WIRE DIAgRAM
Wire connections shown in Fig. 1 are described hereunder:
Terminals
Function
L-N-GND
Power supply
MOT-COM-MOT
Motor
N-BLINK
LAMP
SWO
SWO
SWC
SWC
PHOT (CLOSE)
PHOT
STOP
STOP
COM
COM
P.P. (OPEN)
Step-by-Step
24 VAC
24Vac
SCA
SCA
ENC1
ENCODER
SHIELD-ANT
Antenna
Note:
The control unit uses a "P2" key with the same functions of the Step-by-Step push-button. This is useful
to control the automatic system during installation (only with DIP2: OFF).

2) ChECKINg CONNECTIONS

1) Cut off power supply.
2) Manually release the door, move it at around half stroke and lock it again.
3) Reset power supply.
4) Send the step-by-step (P.P.) control signal through the P2 key, P.P. or remote control.
5) The door leaves should open. If not, with stopped motor, it is sufficient to invert the move wires of
the motor (MOT/MOT) of the motor and the limit switches (SWO/SWC).
6) Proceed with regulations described in "STROKE ACQUISITION & SLOWDOWNS"
Description
Input, 230VAC 50Hz (CORE)
Input, 115VAC 50/60Hz (CORE 115V))
(1-Phase/2-Neutral/GND-Ground connection)
Connection to motor:
(MOT-move/COM-Common/MOT-move)
Output, connection to Flashing light
CORE: 230 Vac 40W max.
CORE 115V: 115 Vac 40W max.
Input, OPENING limit switch (Normally Closed contact)
Input, CLOSING limit switch (Normally Closed contact)
Input, connection to safety devices, Normally Closed (N.C.) contact (e.g.
photocells): configurable through DIP3).
In "Service man" mode, it activates the CLOSE function.
In this case connect a Normally Open (N.O.) key.
Input, STOP key (N.C. contact)
Can assume the Close or Pedestrian function (contact N.O.) see "Advanced
Programming" paragraph.
Common, all control inputs.
Input, step-by-step key (N.O. contact). Can assume the OPEN function see
paragraph "Advanced Programming".
In "Service man" mode, it activates the OPEN control function.
Output, 24Vac/200mA max accessory power supply.
Contact free from voltage, not insulated for the connection of open gate
indicator lamp.
Open contact with closed door leaf. Flashing light during the door leaf
movement. With open door leaf, the contact is closed.
Input, connection of the encoder (OPTIONAL).
See section HOW TO ADJUST BRAKING
Connection of the antenna to the incorporated radio-receiver module
(SHIELD-screen/ANT-signal).
EN
11

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis