Short circuit current rating (SCCR)
Suitable for use on a circuit capable of delivering not more than 200 kA rms symmetrical amperes, 230
Volts for INV Mx IV02 or 480 Volts for INV Mx IV01, maximum when protected by fuses.
"Warning" – Use fuses rated 600 V/50 A for INV MA IV02 only.
"Warning" – Use fuses rated 600 V/10 A for INV MA IV01 only.
"Warning" – Use fuses rated 600 V/30 A for INV MB IV01 only.
"Warning" – Use fuses rated 600 V/30 A for INV MC IV01 only.
"Warning" – Use fuses rated 600 V/70 A for INV MD IV01 only.
CAUTION: Integral solid state short circuit protection does not provide branch circuit protection. Branch
circuit protection must be provided in accordance with the Manufacturer Instructions, National Electrical
Code and any additional local codes.
All wiring terminals marked to indicate proper connections for the power supply, load and control circuitry.
The tightening, torque to connect the motor terminals, is 26.55 lB/in (size A to C) and 5.31 lb/in to connect
the PTC (in all sizes).
Instruction for operator and servicing instructions on how to mount and connect the products using
the intended motor connection adapter, please see chapter 3.3 and 9.1 in the operating manual.
CAUTION: Use 75° C copper wires only.
Drives do not provide over temperature sensing.
CAUTION: For Mx IV01 used in Canada: TRANSIENT SURGE SUPPRESSION SHALL BE INSTALLED ON
THE LINE SIDE OF THIS EQUIPMENT AND SHALL BE RATED 277 V (PHASE TO GROUND), 480 V (PHASE
TO PHASE), SUITABLE FOR OVERVOLTAGE CATEGORY III, AND SHALL PROVIDE PROTECTION FOR A
RATED IMPULSE WITHSTAND VOLTAGE PEAK OF 2.5 kV
The Type of branch circuit protection devices used for BREAKDOWN OF COMPONENT TEST is
Nonrenewable Cartridge Fuse, Class _RK5.
As RK5 is the worst Case Type, any other Type can be used.