INSTALLATION
Preparation
1
2
3
4
5
1 Concrete base
2 Impact sound insulation
3 Floating screed
4 Floor covering
5 Recess
9.4

Wall outlet

9.4.1 General
f Always ensure there is enough space for the other supply
f
lines in the wall outlets (see chapter "Specification / Dimen-
sions and connections").
f Route the brine lines through separate wall outlets.
f
f Provide thermal insulation on the brine lines in accordance
f
with applicable regulations.
9.4.2 Wall outlets above ground
f Establish wall outlets in the building wall with a slight fall to
f
the outside (minimum inclination: 1 cm every 30 cm).
f Insert the wall outlets with a slight fall.
f
f Seal the space between the wall and wall outlet with mortar.
f
f Route the brine lines through the wall outlets.
f
f Seal the space between the brine line and wall outlet with a
f
suitable sealant (e.g. well foam). Ensure the brine lines are
centred in the wall outlets.
52
| WPE-I H 400 Premium
9.4.3 Wall outlets below ground
Material losses
!
f Use waterproof wall outlets below the highest
f
groundwater level.
A
3
C
2
3
1 Wall outlet
2 Brine line
3 Mortar
4 Sealant
f Establish wall outlets in the building wall with a slight fall to
f
the outside (minimum inclination: 1 cm every 30 cm).
f Insert the wall outlets with a slight fall.
f
f Cut off the wall outlet from the top downwards at an angle to
f
the building wall.
f Seal the space between the wall and wall outlet with mortar.
f
f Route the brine lines through the wall outlets.
f
f Seal the space between the brine line and wall outlet with a
f
suitable sealant (e.g. well foam). Ensure the brine lines are
centred in the wall outlets.
B
1
D
1
4
www.stiebel-eltron.com