  • DEUTSCH, seite 3
FlameGard 5 Test Lamp
Quick Start Guide
Warning!
The quick start guide does not replace the operating manual. It is imperative
that the operating manual be read and observed when using the device. In
particular, the safety instructions, as well as the information for the use and
operation of the device, must be carefully read and observed.
The operating manual can also be provided as a hard copy upon request.
1) Testing distance
It is important to begin a series of flame detector checks with a fully charged
Test Lamp.
Stand between 3 and 11 m from a Flame Detector that is to be tested and
aim the Test Lamp directly into the detector window.
Press the ON button and be sure the high intensity pulsing beam strikes the
detector face squarely.
On some Flame Detectors shaking the Test Lamp from side to side
or up and down may increase the simulation of flame flicker and
improve the response of the flame detector to the lamp.
GB
MAN5TL-QG/01
loading

Inhaltszusammenfassung für MSA FlameGard 5

  • Seite 3 FlameGard 5 Testlampe Kurzanleitung Warnung! Die Kurzanleitung ist kein Ersatz für die Gebrauchsanleitung. Die Gebrauchsanleitung ist für die Nutzung des Gerätes zwingend zu lesen und zu beachten. Insbesondere die darin enthaltenen Sicherheitshinweise sowie die Angaben zu Einsatz und Betrieb des Gerätes müssen aufmerksam gelesen und beachtet werden.
  • Seite 4 Unter Umständen blinkt auch die grüne LED. Nach einer zeitlichen Verzögerung beginnt die rote LED, schnell zu blinken. Dies zeigt das Ende des Tests an. Die FlameGard 5 Testlampe löst beim Flammendetektor einen Alarm aus. Das System muss während des Tests deaktiviert werden, damit kein falscher Alarm ausgelöst wird.