BTL7-A/E1 _ 0-M _ _ _ _ -K(8)-SA262-K _ _ /F _ _
Micropulse Transducer - Rod Style
6
Calibration procedure
Output
Linear
gradient
transducer
Rising
BTL7-A...
BTL7-E...
Falling
BTL7-A...
BTL7-E...
Tab. 6-1:
Value table for teach-in
6.1

Programming inputs

Programming inputs La and Lb must be used in order to
make settings. A programming input at 20 to 28 V
corresponds to activation (high active).
The Balluff BTL7-A-CB02-... adjusting box can be used for
this (see Accessories on page 21).

Automatic deactivation!

If no signals are transmitted via the
programming inputs for approx. 10 min,
programming mode is automatically ended.
6.2

Calibration procedure notes

Prerequisites
Programming inputs are connected.
The transducer is connected to the system controller.
Voltage or current values from the transducer can be
read (using a multimeter, the system control or the
adjusting box).
The PK conductor of the transducer must
be connected to the RD conductor of the
calibration box!
Fig. 6-1:
Connecting the BTL7-A-CB02-K calibration box to the
BTL7-...-SA262 cable version
12
english
Unit
Min.
Null
value
value
V
−0.5
0
mA
3.6
4.0
V
10.5
10.0
mA
20.4
20.0
Linear transducer
Indication for
Indication
adjustment
for teach-in
2.0
4.0
6.0
12.0
2.0
4.0
6.0
12.0
Values for null and end point
Any desired position of the magnet can be used as the
null or end point. However, the null and end points may
not be reversed.
The absolute null and end points must lie within the
minimum or maximum limits of what can be output
(see value table).
The last set values are always saved, regardless
of whether the setting was ended using the
programming inputs or automatically after
10 min have expired.
Value table for teach-in
The following examples refer to transducers
with 0 to 10 V or 4 to 20 mA output.
RD
Calibration box
YE
YE
GY
GY
8-pin
PK
PK
RD
GN
GN
BU
BU
BN
BN
WH
WH
8-port
luster terminal
End
Max.
Error
value
value
value
10.0
10.5
10.5
20.0
20.4
3.6
0
−0.5
−0.5
4.0
3.6
3.6
Supply
6-pin
Adapter cable with
connector (luster terminal)